Carrier 48AJ User Manual

Page 86

Advertising
background image

86

Table 40 — Occupied Heat and Morning Warm-Up

Operation and Controlling Factors

LEGEND

SPACE TEMPERATURE SENSOR CONTROL — If the unit

is equipped with a field-supplied space sensor and a remote

start/stop switch, constant volume (CV) cooling will operate as

follows: Stage 1 cooling begins when there exists a 1.5° F

demand and ends when the demand returns back to 0.5° F.

Stage 2 cooling begins when there is a 2.0° F demand and will

continue until the demand returns 1.0° F. Stage 2 cannot be en-

ergized until a minimum of eight minutes of Stage 1 operation

or as long as stage 1 is making a reduction in the space temper-

ature trend. If the temperature trends stop improving but the

demand still exceeds 2.0° F, then Stage 2 cooling will be

energized.

When economizer operation is suitable, the control will use

economizer, as the first stage of cooling will bring on the com-

pressor 1 when Stage 2 demand is called for. If supply-air tem-

perature (SAT) remains above supply-air set point (SASP) for

15 minutes after energizing compressor 1, then compressor 2

shall be started. When Stage 2 is satisfied, the last stage of

compression shall be dropped. When Stage 1 is satisfied, the

control will drop all DX cooling.

If the unit is equipped with a field-supplied space sensor and

a remote start/stop switch, CV heating will operate as follows:

Stage 1 heating begins when there exists 1.5° F demand and

ends when the demand returns back to 0.5° F. Stage 2 heating

begins when there is a 2.0° F demand and will continue until

the demand returns to 1.0° F. Stage 2 cannot be energized until

a minimum of eight minutes of Stage 1 operation or as long as

Stage 1 is making an increase in the space temperature trend. If

the temperature trends stop improving but the demand still ex-

ceeds 2.0° F, then Stage 2 heating will be energized
SPACE TEMPERATURE RESET SENSOR (VAV Only) —

An accessory space temperature sensor (T-55 or T-56 without

offset) is required. Space temperature reset is used to reset the

supply-air temperature set point of a VAV system higher, as the

space temperature falls below the Occupied Cool set point. As

the space temperature falls below the Occupied Cool set point,

the supply-air temperature will be reset upward as a function of

the reset ratio. (Default is 3.) Reset ratio is expressed in degrees

change in supply-air temperature per degree of space tempera-

ture change. A reset limit will exist which will limit the maxi-

mum number of degrees the supply-air temperature may be

raised. (Default is 10 F.) Both the reset ratio and the reset limit

are user definable. The sequence of operation is as follows:

1. The on/off status of the unit supply fan is determined.
2. If the fan is ‘‘on,’’ the sequence will check if the system is

occupied.

3. If the system is in Occupied mode, the sequence will de-

termine if the reset option is enabled.

4. If the reset option is enabled, the sequence will read the

space temperature and compare it to the Occupied Cool

set point. If the temperature is below the Occupied Cool

set point, the algorithm will compute the reset value and

compare this value against the reset limit. If it is greater

than the reset limit, the sequence will use the reset limit as

the reset value. See Fig. 61.

NOTE: A computer equipped with Carrier network access

software (ComfortWORKS®, Building Supervisor, or Service

Tool) or an accessory Remote Enhanced Display is required to

enable this function.
Space Temperature Reset Example — The occupied cooling

set point is set to 73 F. The Reset Ratio is set to 5. The Reset

Limit is set to 20 F. The Reset Ratio determines how many de-

grees F the temperature is reset. At 72 F, the supply tempera-

ture will be reset 5 degrees higher. At 71 F, the supply tempera-

ture will be reset 10 degrees higher. At 70 F, the supply temper-

ature will be reset 15 degrees higher. At 69 F, the supply

temperature will be reset 20 degrees higher and the Reset Limit

will have been reached.

SOFTWARE

VERSION

OCCUPIED

HEAT

ENABLED

VIA

MORNING
WARM-UP

MAY START

DURING

TEMPERATURE

CONDITION

FOR HEAT

TO START

3.0 and Later DIP switch no. 5

Smart start or

within

10 minutes

RAT < OHSP

OHSP — Occupied Heat Set Point
RAT

Return-Air Temperature

BASE MODULE

CONTROL BOARD

(+) T11

(-) T12

4-20 mA

INPUT

FIELD

SUPPLIED

INPUT DEVICE

Fig. 61 — Space Temperature Reset Wiring

mA INPUT

DEG. F RESET

4

0.00

5

1.25

6

2.50

7

3.75

8

5.00

9

6.25

10

7.50

11

8.75

12

10.00

13

11.25

14

12.50

15

13.75

16

15.00

17

16.25

18

17.50

19

18.75

20

20.00

LEGEND
T — Terminal
NOTE: The 4 to 20 mA input is a field-supplied non-Carrier EMS
(Energy Management System) device.

Advertising
This manual is related to the following products: