ECONOMIZER SETTINGS
Accessory Enthalpy Control (Fig. 46) — The control

(HH57AC077) is mounted in the economizer hood. See

Fig. 37. The enthalpy setting adjustment is on the enthalpy con-

trol. For maximum benefit of outdoor air, set enthalpy control

to A. See Fig. 47 and 48.

The enthalpy controls operation of the economizer outdoor-

air damper to provide free cooling on a signal form the cooling

thermostat.
Enthalpy Control Installation — The outdoor air enthalpy

control is installed on the inside panel of the outdoor air hood.

The enthalpy control should be mounted when the outdoor air

hoods are assembled. To install the control, perform the follow-

ing procedure:

1. Turn off all power. Ensure disconnect is locked out.
2. Remove the economizer inlet filters from the bottom of

the right hand economizer hood. See Fig. 37. See Fig. 49

for economizer details.

3. Mount the outdoor air enthalpy sensor inside the right

economizer hood on the right side panel of the hood, ad-

jacent to the outdoor-air thermistor.

4. Locate the red, violet, and brown wires near the outdoor

air thermistor. Remove the splice from the red and violet

wires. Remove the cap from the brown wire.

5. Install a

1

/

4

-in. push on terminal (field-supplied) on the vi-

olet and brown wires.

6. Connect a

1

/

4

-in. push on terminal (field-provided) to one

end of a 18-gage, 6-in. jumper wire (field-provided).

Connect the other end to the red wire and attach a

1

/

4

-in.

push on connector (field-provided).

7. Connect the red wire with the jumper to terminal TR1.

Connect the jumper to terminal 2. Connect the brown wire

to terminal TR. Connect the violet wire to terminal 3. All

connections are on the enthalpy control.

8. Replace the economizer filters.
9. Return power to unit.

Accessory Differential Enthalpy Control (Fig. 46) — The

control (HH57AC077), in conjunction with the accessory en-

thalpy sensor (HH57AC078), controls economizer operation

according to the differential enthalpy. The control is mounted

in the economizer hood. The sensor is mounted in the return

duct (48AJ,AK and 48EJ,EK) or return air plenum (48AW,AY

and 48EW,EY).
Differential Enthalpy Sensor Installation — To install the

control, perform the following procedure:

1. Turn off all power. Ensure disconnect is locked out.
2. Remove the economizer inlet filters from the bottom of

the right hand economizer hood. See Fig. 37 and 49.

3. Remove the factory-installed, 620-ohm jumper between

terminals SR and + on the enthalpy control located inside

the outdoor air hood.

4. Connect the violet wire from the enthalpy sensor kit to

the + terminal on the enthalpy control. Connect the blue

wire from the enthalpy sensor kit to the SR terminal on

the enthalpy control.

5. Turn the enthalpy control set point potentiometer clock-

wise past the ‘‘D’’ setting on the enthalpy control to con-

figure the control to operate on differential enthalpy. See

Fig. 47.

6. Remove the return-air enthalpy sensor from the accessory

package. Using the screws provided, mount the sensor in-

side the return duct near the unit. Do not locate the control

too far from the unit, or the wires will not reach from the

sensor to the control. On 48AW,AY and 48EW,EY units,

the enthalpy sensor can be installed in the return air sec-

tion of the unit, under the return air dampers.

MOUNTING ANGL
(WITHOUT TABS)

FILTER TRACK
ASSEMBLY

BLACK SEAL STRIP
(CENTERED)

FILTER COVER

MOUNTING ANGLE
(WITH TABS)

Fig. 43 — Mounting Angle (Without Tabs)

Attached to Filter Track Assembly

Fig. 44 — Mounting Angle (With Tabs) Attached to

Filter Track Assembly

Fig. 45 — Attaching Seal Strip to Filter Cover