Table 7 — Electrical Data — 48AJ,AK,AW,AY Units (cont)

LEGEND

*Fuse or HACR circuit breaker per NEC.

NOTES:
1. In compliance with NEC requirements for multimotor and combi-

nation load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker. The Canadian units may be fuse or circuit breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%.
Use the following formula to determine
the percent of voltage imbalance.
% Voltage imbalance

Example: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

= 457

Determine maximum deviation from average voltage.

(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v

Maximum deviation is 7 v.
Determine percent of voltage imbalance.

% Voltage Imbalance = 100 x

= 1.53%

This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.

UNIT SIZE

48AJ,AK,

AW,AY

NOMINAL

VOLTAGE

(3 PH, 60 Hz)

VOLTAGE RANGE

COMPRESSOR

OFM

IFM

POWER

EXHAUST

POWER

SUPPLY

No. 1

No. 2

Min

Max

RLA LRA RLA LRA Qty FLA Hp

FLA

FLA

(total)

MCA

MOCP*

050

208/230

187

253

69.2

345

69.2

345

4

5.3

(ea)

20

59.4/54.0

236.3/230.9

300/300

23.6/23.6

259.9/254.5

300/300

25

74.8/68.0

253.1/244.9

300/300

23.6/23.6

276.7/268.5

350/300

30

88/80.0

269.6/259.6

350/300

23.6/23.6

293.2/283.2

350/350

460

414

508

28.8

173

28.8

173

4

2.7

(ea)

20

27

102.6

125

12.6

115.2

125

25

34

110.9

125

12.6

123.5

150

30

40

118.4

150

12.6

131.0

150

575

518

632

26.7

120

26.7

120

4

2.4

(ea)

20

22

91.7

110

12.6

104.3

125

25

27

96.8

110

12.6

109.4

125

30

32

103.0

125

12.6

115.6

125

060

208/230

187

253

82.1

446

82.1

446

6

5.3

(ea)

25

74.8/68.0

291.3/284.5

350/350

35.4/35.4

326.7/319.9

400/400

30

88/80.0

306.0/296.5

350/350

35.4/35.4

341.4/331.9

400/400

40

114/104

338.5/326.0

450/400

35.4/35.4

373.9/361.4

450/450

460

414

508

43.6

223

43.6

223

6

2.7

(ea)

25

34

148.3

175

18.9

167.2

200

30

40

154.3

175

18.9

173.2

200

40

52

168.4

200

18.9

187.3

225

575

518

632

34.6

164

34.6

164

6

2.4

(ea)

25

27

119.3

150

18.9

138.2

150

30

32

124.3

150

18.9

143.2

175

40

41

134.9

175

18.9

153.8

175

FLA

Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration
IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA — Minimum Circuit Amps
MOCP— Maximum Overcurrent Protection
NEC — National Electrical Code
OFM — Outdoor (Condenser) Fan Motor
RLA

Rated Load Amps

= 100 x

max voltage deviation from average voltage

average voltage

Average Voltage =

452 + 464 + 455

3

=

1371

3

IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.

7
457