EVCO EPU2BXP1S1 User Manual

Page 10

Advertising
background image

EVCO S.p.A.

c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104

EVCO

page 10 of 68

AI 7

Not used

AI 8

Not used

AI 9

Not used

Serial ports

RS485

RS485 Modbus RTU

CAN bus

To Vgraph

Digital inputs

DI 1

Presence sensor

DI 2

Start – Stop (remote)

DI 3

Supply fan thermal protection

DI 4

Return fan thermal protection

DI 5

Not used

DI 6

Not used

DI 7

Not used

DI 8

Not used

DI 9

Not used

Analogue outputs

AO 1

Not used

AO 2

Not used

AO 3

Recovery heat exchanger BY-PASS damper control (0-10 V) *

AO 4

Not used

AO 5

Not used

AO 6

Mixing room damper control (0-10 V)

Digital Outputs (Relay)

DO 1

Return fan first speed

DO 2

Return fan second speed

DO 3

Return fan third speed

DO 4

Supply fan first speed

DO 5

Supply fan second speed

DO 6

Supply fan third speed

DO 7

Recovery heat exchanger BY-PASS damper control *

DO 8

Not used

DO 9

Not used

(*) The recovery heat exchanger BY-PASS damper control can be analogic or digital, and

setting with clock

RTC system clock - Real Time Clock.

For driving the 3-speed fans (Digital output) set PG10=DO