Modulation of the air flow with CO

2

probe

This function is enabled only at the times COMFORT. It provides for the modulation of fan speed according to the value

read by the probe of

CO

2

and is activated by setting PF01 = 3. The speed modulation takes place according to a PI

control (if PF17 = 0 only proportional control).

PF16 = 1 with parameter adjustment is a ramp like the following:

In case of parameter PF16 = 0 the adjustment is in steps, the steps are calculated according to the previous ramp broken within the

values indicated by the parameters PF21 (value variable speed corresponding to the speed V1), PF22 (value variable speed

corresponding to the speed V2 ), PF23 (value variable speed corresponding to the speed V3)

Note: To use this feature, you must enable the CO2 probe (parameter PH42 = 1) and the relative values of linearization (parameters

PH03 and PH04).

6.8.8

A

djusting

the static pressure

This feature provides for the modulation of the fan speed as a function of the pressure of canale.e is activated by setting PF00 = 1. The

speed modulation takes place according to a PI control (if PF37 = 0 only proportional control).

The static pressure setpoint supply air is moved up slowly from 0 to the setpoint target when you start the central

unit. The ramp time is defined by parameter PF32, setpoint adjustment ramp static pressure.

PF30: minimum fan speed

PF31: maximum fan speed

PF32: Adjust the static pressure setpoint ramp

PF14:Set

0%

CO

2

PF15: Diff

100%

PF31

Max Vel.

-Pb/2

+Pb/2

Fan Speed

PF30

Min Vel.

Pressure (Pa)

Setpoint