EVCO EPU2BXP1S1 User Manual

Page 37

Advertising
background image

EVCO S.p.A.

c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104

EVCO

page 37 of 68

PH04

Maximum CO

2

probe PPM value

1100

PH03

10000

ppm

IS-V

PH05

Enables unit switch-on/off from

“Start/Stop” digital input

Yes (1)

No (0)

Yes (1)

-

IS-V

PH06

Enables unit switch-on/off from supervisor

No (0)

No (0)

Yes (1)

-

IS-V

PH07

Minimum value Pa pressure probe

0

0

32000

Pa

IS-V

PH08

Maximum value Pa pressure probe

3000

0

32000

Pa

IS-V

PH18

Clear hystorical alarms

NO (0)

NO (0)

YES (1)

-

IS-V

Set YES (1)

ad wait for

the NO (0)

PH20

Enable buzzer

Yes (1)

No (0)

Yes (1)

-

IS-V

PH30

Temperature unit of measurement

0: °Celsius

1: °Fahrenheit

0 (°C)

0 (°C)

1 (°F)

-

IS-V

PH32

Language of user interface

(English, Italian, French)

ENG

ENG

FRE

-

IS-V

PH99

Reset the factory parameters default

NO (0)

NO (0)

YES (1)

-

IS-D

Wait for the

NO (0)

value to be

read again

on reset

completion

PSd2

Installer level password (2)

0

-999

9999

-

IS

Level 3

MANUFACTURER MENU

CONFIGURATION PARAMETERS

After modification of these parameters it is recommended to remove and then re-apply the power supply to the board.

PG00

Unit type:

1=Compact

2=Complete

2

1

2

-

CO-G

PG01

Enabling bypass recuperation

Yes (1)

No (0)

Yes (1)

-

CO-G

PG02

Selection of type of device for heating:

0: Disabled

1: Hot water coil only

2: Electric heater DO coil only

3: Electric heater AO coil only

3

0

3

-

CO-G

PG03

Type of recovery heat exchanger by-pass

damper control:

0: Digital Control (DO7)

1: Analogue Control (AO3)

DO (0)

DO (0)

AO (1)

-

CO-G

PG04

Outside air damper enabling

Yes (1)

No (0)

Yes (1)

-

CO-G

PG05

Enabling of post-ventilation

Yes (1)

No (0)

Yes (1)

-

CO-G

PG06

Enabling of recovery heat exchanger anti-

freeze protection

Type 1

(1)

Disabled

(0)

Type 2 (2)

-

CO-G

PG08

Enabling of recovery heat exchanger by-pass

in summer

Yes (1)

No (0)

Yes (1)

CO-G

PG09

Activation of outside air damper end run

Yes (1)

No (0)

Yes (1)

CO-G

PG10

Type of fan

DO (0)

DO (0)

AO (1)

-

CO-G

If PF00=1

PG10=1