6.7

Functionality of the COMPACT control solution

This control solution offers the base functionality present also in the "complete" solution.

6.7.1

Supply and return fans

The program manages two fans, supply and return. For the two fans is expected to ON / OFF control with three steps

or analog output. . The working is the same for both fan except for the case of Recovery heat exchanger antifreeze

protection and in function with two pressure probes.

The adjustment is based on the parameter distinct PF01, which distinguishes a manual adjustment with automatic and

automatic sensor signal is likely:

PF01=0 manual regulation

PF01=1 automatic regulation without presence sensor

PF01=2 automatic regulation with presence sensor

PF01=3 automatic regulation with CO2 sensor

La regolazione può controllare direttamente la velocità dei ventilatori (PF00=0), oppure controllare la portata dei

ventilatori (PF01=1).

If the speed is controlled all the configuration parameters will modify directly the speed of the fans

(PF02/PF03/PF04/PF05/PF12/PF13) with a choice V1/V2/V3. Instead in the case of flow control these parameters will

be to choose the setpoint adjustment V1/V2/V3 pressostativa (PF33/PF34/PF35).

In ON/OFF regulation (parameter PG10=0) the 3 speeds (V1, V2, V3) are activated each by a dedicated relay.

In regulation with speed variator inverter (parameter PG10=1) the three speeds are determined by the value defined

by the parameters PF21, PF22 and PF23, or it can run in the complete control of the ramp (see the sections on

Regulations).

6.7.1.1

Manual regulation

The fans work at the MANUAL Speed/capacity set via the PF02 parameter.

6.7.1.2

Automatic regulation without presence sensor

Two time periods are defined: ECONOMY time band and COMFORT time band. A working speed is defined for each

time period, respectively ECONOMY Speed/capacity (parameter PF04) and COMFORT Speed/capacity (parameter

PF03). The fans are controlled at the Speed/capacity defined in the relevant time periods. The following parameters

must be used

PT01: start of COMFORT time band.

PF03: fans Speed/capacity in COMFORT band.

PT02: start of ECONOMY time band.

PF04: fans Speed/capacity in ECONOMY band.

For each day of the week it is possible to define whether this day is a working or non-working day, parameters

PT11=Sunday, PT12, PT13, PT14, PT15, PT16, PT17):

- Working days: the regulation is the normal automatic type for ECONOMY e COMFORT time period;

- Non-working days: the Speed/capacity are determined by parameter PF13, due to defect V0.

Note: If the RTC system clock is in alarm condition it is possible to set the PF05 parameter to determine at which

speed both fans must function.