EVCO S.p.A.

c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104

EVCO

page 32 of 68

PF10

Differential for the by-pass of the recovery

unit damper in anti-freeze protection

mode

2.0

0.0

20.0

36.0

°C

°F

CO-F

PF11

Fans working time in post-ventilation

mode

30

0

999

Sec

CO-F

OUTSIDE AIR DAMPER

This menu is only accessible if PG04=1

PS01

Fans switch-on delay from outside air

damper activation

45

0

999

Sec

CO-SE

Reading

only

PS02

Outside air damper switch-OFF delay from

fans switch-off

15

0

999

Sec

CO-SE

PS05

Delay of outside air damper end run

60

0

999

Sec

CO-SE

PS06

Enable FreeHeating

0: No

1: Yes

No (0)

No (0)

Yes (1)

CO-SE

PS07

Type damper control mixing room

0: Free-Heating only

1: Regulating air quality only

2: Priorities on demand higher of the two

3: Average of the two requests

4: Fixed open

0

0

4

CO-SE

PS08

Minimum aperture shutter

mixing room

20.0

0.0

PS09

%

CO-SE

PS09

Maximum aperture shutter mixing

chamber

100.0

PS08

100.0

%

CO-SE

PS10

Fixed value of damper opening

50.0

0.0

100.0

%

CO-SE

PS12

Differential which enables free-cooling

and free-heating temperature

2.0

0.0

20.0

°C

CO-SE

PS13

Setpoint differential which enables free-

cooling and free-heating temperature

4.0

0.0

20.0

°C

CO-SE

PS15

Opening the minimum and maximum

damper

0:

Disabled

1: Only internal bandwidth

2: Always

2

0

2

CO-SE

PS20

Setpoint - adjusting the air quality

600

0

10000

ppm

CO-SE

PS21

Differential - adjusting the air quality

100

0

2000

ppm

CO-SE

RECOVERY HEAT EXCHANGER

Pr01

Anti-freeze temperature minimum

setpoint

1.0

PH01

PH02

°C

°F

CO-RH

Used only if

PG06 = 2

Pr02

Anti-freeze temperature minimum

differential

2.0

0.0

0.0

20.0

36.0

°C

°F

CO-RH

Pr03

Recovery heat exchanger by-pass cycle

time for cyclical defrosting

5

1

99

Min

CO-RH

ALARM PARAMETERS

PA03

Enabling of supply/return fans thermal

overload alarm

Active

(1)

Not-active

(0)

Active (1)

-

CO-S