c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104

EVCO

page 39 of 68

PS08

Minimum

opening

damper mixing room

20.0

0.0

PS09

%

CO-SE

PS09

Maximum

opening

damper mixing room

100.0

PS08

100.0

%

CO-SE

PS10

Fixed value of damper open

50.0

0.0

100.0

%

CO-SE

PS12

Differential which enables free-cooling and

free-heating temperature

2.0

0.0

20.0

°C

CO-SE

PS13

Setpoint differential which enables free-

cooling and free-heating temperature

4.0

0.0

20.0

°C

CO-SE

PS15

Minimum and maximum

opening

damper

0: Disabled

1:

Only internal bandwidth

2: Always

2

0

2

CO-SE

PS20

Setpoint - Regulation the air quality

600

0

10000

ppm

CO-SE

PS21

Differential - Regulation the air quality

100

0

2000

ppm

CO-SE

RECOVERY HEAT EXCHANGER

Pr01

Anti-freeze temperature minimum setpoint

1.0

PH01

PH02

°C

°F

CO-RH

Used only if

PG06=2

Pr02

Anti-freeze temperature minimum differential

2.0

0.0

0.0

20.0

36.0

°C

°F

CO-RH

Pr03

Recovery heat exchanger by-pass cycle time

for cyclical defrosting

5

1

99

Min

CO-RH

ALARM PARAMETERS

PA03

Enabling of outlet/return fans thermal switch

alarm

Active (1)

Not-

active

(0)

Active

(1)

-

CO-S

PA05

Enabling of differential pressure switch alarm

Active (1)

Not-

active

(0)

Active

(1)

Sec

CO-S

PA06

Delay of differential pressure switch alarm

10

0

999

Sec

CO-S

PA08

Signals differential pressure switch alarm on

alarm relay

Yes (1)

No (0)

Yes (1)

Sec

CO-S

Only if PG02=0

PA09

Anti-freeze alarm active on hot water coil

Not-

active (0)

Not-

active

(0)

Active

(1)

Sec

CO-S

PA10

Anti-freeze alarm delay on hot water coil

10

0

999

Sec

CO-S

PA12

Activates the heaters thermal overload alarm

Active (1)

Not-

active

(0)

Active

(1)

Sec

CO-S

Only if

PG02>=2

PA13

Signals heaters thermal switch alarm on

alarm relay

Yes (1)

No (0)

Yes (1)

CO-S

Only if

PG02

>

=2

PA16

Enable supply high temperature alarm from

transducer

Active (1)

Not-

active

(0)

Active

(1)

CO-S

PA17

Supply high temperature alarm setpoint

85.0

PH01

PH02

°C

°F

CO-S

PA19

Supply high/low temperature alarms

differential

3.0

0.0

0.0

20.0

36.0

°C

°F

CO-S

PA20

High/low temperature alarms delay

10

0

999

Sec

CO-S