c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104

EVCO

page 33 of 68

PA05

Enabling of differential pressure switch

alarm

Not-

active

(0)

Not-active

(0)

Active (1)

Sec

CO-S

PA06

Delay of differential pressure switch alarm

10

0

999

Sec

CO-S

PA08

Signals differential pressure switch alarm

on alarm relay

No (0)

No (0)

Yes (1)

Sec

CO-S

Only if

PG02=0

PA09

Anti-freeze alarm active on hot water coil

Not-

active

(0)

Not-active

(0)

Active (1)

Sec

CO-S

PA10

Anti-freeze alarm delay on hot water coil

10

0

999

Sec

CO-S

PA12

Activates the heaters thermal switch alarm

Not-

active

(0)

Not-active

(0)

Active (1)

Sec

CO-S

Only if

PG02>=2

PA13

Signals heaters thermal overload alarm on

alarm relay

No (0)

No (0)

Yes (1)

CO-S

Only if

PG02=2

PA16

Enable supply high temperature alarm

from transducer

Not-

active

(0)

Not-active

(0)

Active (1)

CO-S

PA17

Supply high temperature alarm setpoint

85.0

PH01

PH02

°C

°F

CO-S

PA19

Supply high/low temperature alarms

differential

3.0

0.0

0.0

20.0

36.0

°C

°F

CO-S

PA20

High/low temperature alarms delay

10

0

999

Sec

CO-S

PA22

Expansion alarm delay

5

0

999

Sec

CO-S

PA24

RTC alarm enabling

Active

(1)

Not-active

(0)

Active (1)

-

CO-S

PA26

Probes alarms signals delay

10

0

240

Sec

CO-S

PA51

Type of alarm fire/smoke

0: Not-active

1: Off by allarm

2: Forcing 1

3: Forcing 2

1

0

3

-

CO-S

VARIOUS PARAMETERS

PH11

Board Modbus address

1

1

247

-

CO-V

PH12

Communication Baud Rate for the board

(0=1200, 1=2400, 2=4800, 3=9600,

4=19200)

3

0

4

-

CO-V

PH13

ModBus Parity (0=none, 1=Odd, 2=Even)

2

0

2

-

CO-V

PH14

Stop Bit ModBus (0=1bit, 1=2bit)

0

0

1

-

CO-V

PH40

Enable supply temperature probe

No (01)

No (0)

Yes (1)

-

CO-V

PH41

Enable return temperature probe

No (0)

No (0)

Yes (1)

-

CO-V

PH42

Enable CO

2

probe (0-5V)

No (0)

No (0)

Yes (1)

-

CO-V

PH43

Enable outside air temperature probe

No (0)

No (0)

Yes (1)

-

CO-V

PH44

CO

2

sensor probe

0: 0-20mA

1: 4-20mA

2: 0-5V

0-10V

(3)

0-20mA

(3)

0-10V (3)

-

CO-V