EVCO EPU2BXP1S1 User Manual

Page 35

Advertising
background image

EVCO S.p.A.

c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104

EVCO

page 35 of 68

Working

Working

Not Working

PT17

Saturday

0

Working

0

Working

1

Not Working

OR

MAINTENANCE

PM01

Functioning hours maximum limit for fans.

The relevant alarm will be triggered over

this limit

8000

0

100000

Hours

IS-MA

PM02

Outlet fan functioning hours

0

0

100000

Hours

IS-MA

PM03

Return fan functioning hours

0

0

100000

Hours

IS-MA

PM90

Last date on which maintenance was

performed on the machine

IS-MA

PM11

Calibration of the anti-freeze air

temperature probe

0.0

-10.0

-18.0

10.0

18.0

°C

°F

IS-MA

PM12

Calibration of the outlet air temperature

probe

0.0

-10.0

-18.0

10.0

18.0

°C

°F

IS-MA

PM13

Calibration of the return air temperature

probe

0.0

-10.0

-18.0

10.0

18.0

°C

°F

IS-MA

PM14

Calibration of the CO

2

probe

0.0

-200

200

ppm

IS-MA

PM15

Calibration of the outside air introduction

temperature probe

0.0

-10.0

-18.0

10.0

18.0

°C

°F

IS-MA

PM16

Calibration of the pressure probe 1

0.0

-200

200

ppm

IS-MA

PM17

Calibration of the pressure probe 2

0.0

-2000

2000

Pa

IS-MA

FANS

PF00

Type of fans control:

0: Speed

1: Capacity

0

0

1

-

IS-F

PF01

Type of fans regulation:

0: Manual

1: Automatic

2: Automatic with presence sensor

3: Automatic with CO

2

sensor

0

0

3

-

IS-F

PF03

Fans Speed/Capacity in COMFORT period

V2

V1

V3

-

IS-F

PF04

Fans Speed/Capacity in ECONOMY period

V1

V0

V2

-

IS-F

PF05

Fans Speed/Capacity in RTC error

V0

V0

V3

-

IS-F

Only if

PF01=1/2/3

PF12

Fans Speed/Capacity in COMFORT with

presence sensor active

V3

V1

V3

-

IS-F

PF13

Speed/Capacity in case of « non working »

day

V0

V0

V3

-

IS-F

PF14

Set point CO

2

probe

500

PH03

PH04

ppm

IS-F

PF15

Proportional band CO

2

probe

600

0

1000

ppm

IS-F

PF16

Type of CO

2

regulation

0

0

1

IS-F

If PF00=1

PF16=1

PF17

Integral time CO

2

regulation

0

0

300

sec

IS-F

PF21

Speed variator value corresponding to speed V1

33.50

0.00

100.00

%

IS-F