Regulations, 1 state of the unit – EVCO EPU2BXP1S1 User Manual

Page 42

Advertising
background image

EVCO S.p.A.

c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104

EVCO

page 42 of 68

6.

REGULATIONS

6.1

State of the unit

There are several unit switch-on/off procedures:

1)

Via the relevant ON/OFF key

Switch-ON: press the relevant key for about 2 seconds, if all the conditions are fulfilled the unit starts working

(“ON” mode).

Switch-OFF: press the relevant key for about 2 seconds, the unit stops working (“OFF” mode).

2)

Using the Start/Stop from digital input control (parameter, PH05=1)

Switch-ON: close the contact, if all the conditions are fulfilled the unit starts working (“ON” mode).

Switch-OFF: if the contact is open the unit stops working (“OFF from Start/Stop” mode).

3)

Via Supervision protocol (parameter, PH06=1)

Switch-ON: activate the switch-on state from protocol, if all the conditions are fulfilled the unit starts working

(“ON” mode).

Switch-OFF: if deactivated by switch-on state protocol the unit stops working (“OFF from Supervisor” mode).

The ON/OFF status from key has priority with respect to the other two. In fact the ON/OFF states by digital input and

supervision protocol can only be reached with machine in “ON” mode.

A machine switched-off by Start/Stop digital input can:

⋅

pass to the OFF state from key (by pressing ESC).

⋅

pass to the OFF state from supervisor if the OFF condition from digital input returns and the OFF state is set

by supervisor.

⋅

ass to the ON state if the ON condition from digital input returns and the OFF state is not set by supervisor.

A unit switched-OFF by supervision protocol can:

⋅

Move to the OFF state by key (by pressing ESC key).

⋅

Move to the OFF state from digital input if the OFF condition from supervisor ceases and the OFF state from

digital input is triggered.

⋅

Move to the ON state if the OFF condition from supervisor ceases and the OFF state is not present from digital

input.

The unit ON/OFF key is the ESC key pressed for about 2 seconds.

The remote Start/Stop input (when present) can be configured using the parameters:

-

PH05: Enables the function

-

PH52: Sets the NC, NO logic for the digital contact