After the (parameter Pr03) delay the by-pass damper is activated to allow defrosting. As soon as the exhaust air

temperature is back above the accepted value the damper is deactivated and the recovery heat exchanger starts

again.

Note: If the anti-freeze probe is in alarm condition the function is disabled.

6.8

Features of the COMPLETE control solution

Al functions of the COMPACT version are included in this version.

Below are listed only the additional features of the COMPLETE control solution.

6.8.1

Post-Ventilation

By setting the parameter PG05=1 it is possible to decide whether to run the fans for a time configured on parameter

PF11, also after unit switch-OFF. If the function is active when the unit stops the fans keep working for further PF11

seconds.

6.8.2

Differential pressure switch

The lack of air flow is signalled via the DI5 Differential Pressure switch digital input. The pressure switch status is

considered after the initial start-up phase of the unit (the length of this phase is configured by parameter PA06). On

expiry of this time if the contact signals a lack of air flow the alarm is signalled immediately. During normal working

the differential pressure switch is monitored continuously. If the contact signals a lack of flow for a period exceeding

the PA06 parameter, the alarm is signalled immediately.

To enable the alarm, set PA05=1.

The differential pressure switch alarm has manual reset. Activation leads to switch-off of the unit taking it into the OFF

due to alarm status.

Unit

ON

OFF

Air Flow

ON

ON

Alarm

PA0

PA0

PA0