EVCO EPU2BXP1S1 User Manual

Page 29

Advertising
background image

EVCO S.p.A.

c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104

EVCO

page 29 of 68

PT14

Wednesday

0

Working

0

Working

1

Not Working

OR

PT15

Thursday

0

Working

0

Working

1

Not Working

OR

PT16

Friday

0

Working

0

Working

1

Not Working

OR

PT17

Saturday

0

Working

0

Working

1

Not Working

OR

Code

Parameter description

Default

Min

Max

UM

Menu

Notes

MAINTENANCE

PM01

Max number of fans working hours.

The relevant alarm occurs over this limit

8000

0

100000

Hours

IS-MA

PM02

Supply fan

working hours

0

0

100000

Hours

IS-MA

PM03

Return fan

working hours

0

0

100000

Hours

IS-MA

PM90

Last maintenance

date

IS-MA

PM11

Anti-freeze air temperature

probe offset

0.0

-10.0

-18.0

10.0

18.0

°C

°F

IS-MA

FANS

PF00

Type of fans control:

0: Speed

1: Capacity

0

0

1

IS-F

PF01

Type of fans regulation:

0: Manual

1: Automatic

2: Automatic with presence sensor

3: Automatic with CO

2

probe

0

0

3

IS-F

PF03

Speed/Capacity fans in

COMFORT period

V2

V1

V3

IS-F

PF04

Speed/Capacity fans in

ECONOMY period

V1

V0

V2

IS-F

PF05

Speed/Capacity fans in RTC error

V0

V0

V3

IS-F

Only if

PF01=1/2/3

PF12

Speed/Capacity fans in COMFORT with

presence sensor active

V3

V1

V3

IS-F

PF13

Speed/Capacity in case of

« non Working » day

V0

V0

V3

IS-F

PF21

Speed variator value corresponding

to speed V1

33.50

0.00

100.00

%

IS-F

PF22

Speed variator value corresponding

to speed V2

66.50

0.00

100.00

%

IS-F

PF23

Speed variator value corresponding

to speed V3

100.00

0.00

100.00

%

IS-F

Advertising