1 manual and automatic reset alarms, 1 manual reset alarms, 2 automatic reset alarms – EVCO EPU2BXP1S1 User Manual

Page 57: 2 alarms table

Advertising
background image

EVCO S.p.A.

c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104

EVCO

page 57 of 68

7.1

Manual and automatic reset alarms

As shown previously there are two types of alarm. Those with manual reset and those with automatic reset. For some

alarms it is possible to set (Alarms Reset) the most suitable type of reset for user needs by means of the relevant

parameters. Other alarms have predetermined reset type.

7.1.1

Manual reset alarms

If a manual rest alarm occurs the alarm icon starts to flash and the buzzer is activated (if configured PH20=1).

Once the conditions for which the alarm has occurred are reset it is possible to manual reset the alarm. To perform

this operation:

Enter the relevant alarm page

hold the ENTER key down for about 2 seconds.

At this point, if there are no other active alarms, the page indicating “NO ALARMS” will be displayed, the icon

disappears, the buzzer switches off and the unit starts working normally. If there are other active alarms the page

relevant to the next active alarm will be displayed.

The consequences relevant to an active manual reset alarm remain valid until the user reset the alarm message.

7.1.2

Automatic reset alarms

If an automatic reset alarm occurs the alarm icon starts to flash and the buzzer is activated (if configured PH20=1).

Once the conditions for which the alarm occurred are reset the alarm message and the relevant consequences are

reset automatically without need of user intervention.

7.2

Alarms table

Below is a list of all alarms managed by the application. The order of presentation is the same as the order of active

alarms occurrence. The alarms can be displayed also with the machine in OFF status.

Code

Alarm description

Reset

Consequence

Delay

AL01

Supply fan thermal overload

(*1)

Automatic

Switches all devices off

Fixed 2 s

AL02

Return fan thermal overload

(*1)

Automatic

Switches all devices off

Fixed 2 s

AL03

Differential pressure switch

(*1)

Manual

Switches all devices off

Selectable

AL04

Hot water coil anti-freeze

Automatic

-

Open the hot water valve

completely

-

Close the fresh air damper

-

Switches fans OFF

Selectable

AL05

Electric heaters thermal overload – manual

reset

Manual

Switches the heaters OFF

Fixed 2 s

AL06

Outside air damper limit switch “completely

open”

(*1)

Manual

Switches all devices off

Selectable

Outside air damper limit switch “completely

closed”

(*1)

AL07

Electric heaters thermal overload – automatic

reset

Automatic

Switches the heaters OFF

Selectable

AL09

Supply fan running hours

Manual

(*2)

Signalling only

-

AL10

Return fan running hours

Manual

(*2)

Signalling only

-