3.1.2

I/O Configuration with 1-speed fans with more speed

variator

c-pro 3 hecto + CAN with 2 A/O V+V

I/O

Description

Analogue inputs

AI 1

Anti-freeze Temperature Probe (Recovery heat exchanger By-Pass) NTC

AI 2

Not used

AI 3

Not used

AI 4

Not used

AI 5

Not used

AI 6

Not used

AI 7

Not used

AI 8

Not used

AI 9

Not used

Serial ports

RS485

RS485 Modbus RTU

CAN bus

To Vgraph

Digital inputs

DI 1

Presence sensor

DI 2

Start – Stop (remote)

DI 3

Supply fan thermal protection

DI 4

Return fan thermal protection

DI 5

Not used

DI 6

Not used

DI 7

Not used

DI 8

Not used

DI 9

Not used

Analogue outputs

AO 1

Not used

AO 2

Not used

AO 3

Recovery heat exchanger BY-PASS damper control (0-10 V) *

AO 4

Return fan control signal (0-10 V)

AO 5

Supply fan control signal (0-10 V)

AO 6

Mixing room damper control (0-10 V)

Digital Outputs (Relay)

DO 1

Return fan (speed 0) enabling

DO 2

Supply fan (speed 0) enabling

DO 3

Not used

DO 4

Not used

DO 5

Not used

DO 6

Not used

DO 7

Recovery heat exchanger BY-PASS damper control *

DO 8

Not used

DO 9

Not used

(*) The recovery heat exchanger BY-PASS damper control can be analogic or digital, and

setting with clock