EVCO EPU2BXP1S1 User Manual

Page 17

Advertising
background image

EVCO S.p.A.

c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104

EVCO

page 17 of 68

3.2.2

I/O Configuration with 1 speed fans + speed variator

c-pro 3 micro SAVE/ c-pro 3 kilo SAVE

I/O

Description

Analogue inputs

AI 1

Anti-freeze Temperature Probe (Recovery heat exchanger By-Pass) - NTC

AI 2

Supply Air Temperature Probe - NTC

AI 3

Return Air Temperature Probe - NTC

AI 4

Outdoor Air Temperature Probe - NTC

AI 5

Not used

AI 6

Not used

AI 7

CO

2

probe (0-10 V) (Optional)

AI 8

Pressure probe 1 (0-10 V) (Optional)

AI 9

Pressure probe 2 (0-10 V) (Optional)

Serial ports

RS485

RS485 Modbus RTU

CAN bus

To Vgraph

Digital inputs

DI 1

Presence sensor

DI 2

Start – Stop (remote)

DI 3

Supply fan thermal overload (protection)

(3 in series)

DI 4

Return fan thermal overload (protection)

(3 in series)

DI 5

Differential pressure switch

DI 6

Hot water coil anti-freeze thermostat

DI 7

Fire/Smoke

DI 8

Outside air damper limit switch (full open)

DI 9

Outside air damper limit switch (full closed)

Analogue outputs

AO 1

Not used

AO 2

Hot water coil modulating valve control (0-10 V)

AO 3*

Recovery heat exchanger BY-PASS damper control (0-10 V)

AO 4

Return fan control signal (0-10 V)

AO 5

Supply fan control signal (0-10 V)

AO 6

Mixing room damper control (0-10 V)

Digital Outputs (Relay)

DO 1

Return fan (speed 0)

DO 2

Supply fan (speed 0)

DO 3

Not used

DO 4

Electric heaters step 1

DO 5

Electric heaters step 2

DO 6

Electric heaters step 3

DO 7*

Recovery heat exchanger BY-PASS damper

DO 8

Outdoor air damper

DO 9

Generic alarm (can be configured)

(*) The recovery heat exchanger BY-PASS damper control can be analogic or digital, and

setting with clock