The following tables illustrate the meaning of the connectors.

MODBUS

RS-485 port with Modbus slave communication protocol.

The following drawing illustrates the aspect of the RS-485 port.

The following table illustrates the meaning of the RS-485 port pins.

Pin

Meaning

1

common

2

not connected

3

not connected

4

D0 = B = - (terminal 0 of the transceiver)

5

D1 = A = + (terminal 1 of the transceiver)

6

not connected

7

not connected

8

not connected

The maximum length of the RS-485 port connection cables is 1,000 m (3,280 ft); see also Modbus specifications and

implementation guides Manual (the document is available on the website www.modbus.org).

MICRO-SWITCH

Micro-switch for:

-

connecting the termination of the RS-485 port (120

, 0.25 W); position micro switch 1 in the ON position in order to connect

the RS-485 port termination (connect the termination of the first and last network element termination).