6.

Configuration parameters

Below find the list of all configuration parameters managed by the MCSA application.

A brief description, the range of acceptable values, the unit of measurement and the proposed default value are

supplied for every description.

6.1.1

List of configuration parameters

Label

Parameter description

Default

Min

Max

USER PARAMETERS

OnOff

Machine status

0FF

0FF

ON

Mode

Summer/winter status from keyboard

E

E

I

SetEcoW Z.1

Zone 1 Economy Set-point (I)

16.0

10.0

30.0

SetComW Z.1

Zone 1 Comfort Set-point (I)

19.0

10.0

30.0

SetEcoS Z.1

Zone 1 Economy Set-point (E)

26.0

10.0

30.0

SetComS Z.1

Zone 1 Comfort Set-point (E)

23.0

10.0

30.0

SetMan Z.1

Zone 1 manual Set-point

26.0

10.0

30.0

SetH Z.1

Zone 1 Humidity Set-point

50.0

0.0

100.0

SetEcoW Z.2

Zone 2 Economy Set-point (I)

16.0

10.0

30.0

SetComW Z.2

Zone 2 Comfort Set-point (I)

19.0

10.0

30.0

SetEcoS Z.2

Zone 2 Economy Set-point (E)

26.0

10.0

30.0

SetComS Z.2

Zone 2 Comfort Set-point (E)

23.0

10.0

30.0

SetMan Z2

Zone 2 manual set-point

26.0

10.0

30.0

MAINTENANCE TECHNICIAN PARAMETERS - OPERATION

PM00

Pump maximum operating hours limit. The relative alarm will

be triggered over this limit

20000

0

100000

PM01

Pump operating hours

0

0

100000

PM02

Chiller-HP maximum operating hours limit. The relative alarm

will be triggered over this limit

20000

0

100000

PM03

Chiller -HP operating hours

0

0

100000

PM90

Last date that maintenance was performed on the machine

MAINTENANCE TECHNICIAN PARAMETERS - MANUAL

PM10

Manual/automatic operation of the DO1 output

0: Auto – automatic operation

1: Manu – manual operation

0 (Auto)

0 (Auto)

1 (Manu)

PM11

Manual/automatic operation of the DO2 output

0: Auto – automatic operation

1: Manu – manual operation

0 (Auto)

0 (Auto)

1 (Manu)

PM12

Manual/automatic operation of the DOE output

0: Auto – automatic operation

1: Manu – manual operation

0 (Auto)

0 (Auto)

1 (Manu)

PM13

Manual/automatic operation of the DO4 output

0: Auto – automatic operation

1: Manu – manual operation

0 (Auto)

0 (Auto)

1 (Manu)

PM14

Manual/automatic operation of the DO5 output

0: Auto – automatic operation

1: Manu – manual operation

0 (Auto)

0 (Auto)

1 (Manu)