5.4.1.2

c-pro 3 hecto

CAN configuration via the Vroom

Operate as follows:

1.

Disconnect the device and terminal power supply.

2.

Connect the device to the terminal via the CAN port.

3.

Connect the device and terminal power supply.

4.

Operate on the terminal to set the NW Node parameter according to the MCSA module CAN address used for reference for

the Vroom terminal.

5.

Hold the terminal LEFT and ENTER keys for 2 seconds: the display will show the Network Status menu:

Network Status

Loc

99

OK

> >

1

1

OK

> >

2

2

OK

> >

3

0

-

> >

4

0

-

> >

5

0

-

> >

6.

Press and release the UP or DOWN key to select the device.

7.

Press and release the ENTER key: the display will show the device Main menu.

5.5

Other regulations

5.5.1

Management of the auxiliary utilities (thermostat, hygrostat)

The MCSA module can manage (after configuration) an auxiliary thermostat and hygrostat.

5.5.1.1

Auxiliary thermostat

If a digital input is configured as “Auxiliary thermostat”, the activation of the digital input due to the activation of one

or more thermostats connected in parallel to the input in question causes the activation of the utilities connected to

the MCSA module (pump, mix valve, heat pump/boiler/chiller), similarly to the heat regulation request by one of the

two zones.

In this case, as well as activating the MCSA utilities, the thermostat contact must also activate the head of its

reference zone (not managed by MCSA).

5.5.1.2

Auxiliary hygrostat

If a digital input is configured as “Auxiliary hygrostat” and a relay output is configured as “Auxiliary dehumidifier” the

activation of the input causes the activation of the output and the other utilities used for the dehumidifying function

(pump, mix valve, chiller) if requested by the configuration (PD01=1 – Water use for enabled dehumidification)

5.5.2

Management and setting the anti-grip periodic cycle

The function has the purpose of preventing blocking of the pump and the valve present in the MCSA system during

system standstill periods due to any deposits present in the system or due to the formation of crystalline aggregates

(lime-scale or other) on the pump and valve mechanical seals.

The function automatically activates the pump and valve in sequence if they are at a standstill for at least one week.

The day and time of weekly activation can be set by the user via the appropriate Maintenance technician level

parameters.

The sequence scans the various system utilities every minute (pump and valve): the cycle leads to the 30 second

activation of the element taken into consideration.