DIGITAL INPUTS

Digital inputs (potential-free contacts).

Clamp

Meaning

COM

common digital inputs

DI1

digital input 1

DI2

digital input 2

DI3

digital input 3

DI4

digital input 4

DI5

digital input 5

The maximum length of the digital input connection cables is 100 m (328 ft).

ANALOGUE INPUTS

Analogue inputs. (NTC)

Clamp

Meaning

AI1

analogue input 1

AI2

analogue input 2

AI3

analogue input 3

GND

earth

+5V

0-5 V ratiometric transducers power supply (5 VDC, 40 mA max.)

+24V

transducers power supply 0-20 mA / 4-20 mA / 0-10 V (24 VDC, 120 mA max.)

The maximum length of the analogue input connection cables and that of the transducers power supply is 100 m (328 ft).

The controller incorporates a restorable circuit breaker protection for the power supplies against short circuit and overload.

For the settings relative to the analogue inputs, see chapter 6 “CONFIGURATION”.

PROG

Port for programming and debug.