2 regulation of the flow temperature, 1 management of the flow circulation pump, 3 management of the flow mixing valve – EVCO EPH4DXP1SA User Manual

Page 32

Advertising
background image

EVCO S.p.A.

c-pro 3

hecto MCSA | User manual ver. 2.0 | Code 144MCSAE204

page 32 of 52

It is also possible to decide whether, following activation of the heating/cooling booster, to force the dehumidifier

output to ON status or not.

5.2

Regulation of the flow temperature

5.2.1

Management of the flow circulation pump

Via the appropriate pump parameter they can be managed in the following way:

EXTERNAL: the pump is not managed from the module.

CONTINUOUS: the flow pump will remain activated continuously with system in ON status and in absence of blocking

alarms.

TEMPERATURE REQUEST: the flow pump will be activated on request of at least one of the zone heating/cooling

collectors.

The activation/deactivation of the pump will follow the switch-on/off delay times established via the relevant

parameters.

As well as the request by the zone heating/cooling collectors, the flow circulation pump will be activated for the

following special cycles:

flow line low temperature protection

system anti-freeze protection

anti-grip cycle

The correct operation of the circulation pump is controlled via the digital input associated with the flow switch of the

mixed circuit (consult the relative paragraph for explanation)

5.2.2

Management of the utilities proposed for heating/cooling

Once the water is made to circulate in the system and whenever the flow work set-point is not satisfied, the system

will start a utilities activation request for heating/cooling of the flow water (On-Off remote consent). The request will

remain active until the set-point is satisfied or while the mixing valve remains open (selection from parameter PL21).

If PL21 = 0, the heating/cooling request is deactivated on reaching the flow set; if PL21 = 1, the heating/cooling

request is deactivated with delay defined by PL22 parameter, on complete closure of the mixing valve.

5.2.3

Management of the flow mixing valve

The controller can regulate a mixing valve via a 0-10V proportional analogue output, to control the flow temperature

control.

The mixing valve operating mode can be set for the distinct Summer and Winter operating modes from the following

possibilities:

Valve forced closed: the valve remains always closed during all operations independently from the system operating

conditions.

Valve forced open: the valve remains open at the percentage set while the regulation is active; with regulation off, the

valve is closed.

Valve in modulation mode: mixing valve opening is controlled on the measurement of the flow water temperature with

respect to the regulation set-point.

In the installation phase and on the basis of system features, it will be necessary to set a proportional regulation band

and, if necessary, an integration constant for a PI control.