EVCO EPH4DXP1SA User Manual

Page 45

Advertising
background image

EVCO S.p.A.

c-pro 3

hecto MCSA | User manual ver. 2.0 | Code 144MCSAE204

page 45 of 52

Label

Parameter description

Default

Min

Max

PH47

Kind of humidity sensor (on the controller)

0: 0-20 mA

1: 4-20 mA

2: 0-5 V

3: 0-10 V

3

0

3

MANUFACTURER PARAMETERS

PGUT

Kind of machine

1: Zone 1 (T+H), Zone 2 (T), V-Room

2: Zone 1 (T+H)

3: Zone 1 (T), Zone 2 (T)

1

1

3

PG02

System line pump mode:

0 = Pump not managed by MCSA

1 = Pump activated on regulation request

2 = Pump always active

1

0

2

MANUFACTURER PARAMETERS – CONF. AI

HAI1

Probe 1 configuration:

0: Disabled

1: External temperature

2: Supply (return) temperature

3: Zone 2 Temperature

4: Zone 1 Temperature

5: Zone 1 Humidity

1

0

5

HAI2

Probe 2 configuration

0: Disabled

1: External temperature

2: Supply (return) temperature

3: Zone 2 Temperature

4: Zone 1 Temperature

5: Zone 1 Humidity

2

0

5

HAI3

Probe 3 configuration

0: Disabled

1: External temperature

2: Supply (return) temperature

3: Zone 2 Temperature

4: Zone 1 Temperature

5: Zone 1 Humidity

3

0

5

HAI4

Probe 4 configuration

0: Disabled

1: External temperature

2: Supply (return) temperature

3: Zone 2 Temperature

4: Zone 1 Temperature

5: Zone 1 Humidity

0

0

5

HAIG

Display configuration

0: No

1: V-Room TH

2: V-Room T

1

0

1