Alarms table – EVCO EPH4DXP1SA User Manual

Page 49

Advertising
background image

EVCO S.p.A.

c-pro 3

hecto MCSA | User manual ver. 2.0 | Code 144MCSAE204

page 49 of 52

7.

Alarms Table

Below find a list of the alarms managed by the application. The order of presentation is the same as the order with

which the alarms are presented when active. The alarms can also be all displayed with the machine off.

Code

Description of the alarm

Rearm

Consequence

Delay

AL01

External

temperature

probe

faulty

or

disconnected

Auto

Prevents

the

regulations

depending on the same

Can be set

AL02

Flow/return

temperature

probe

faulty

or

disconnected

Auto

Stops the unit

Can be set

AL03

Zone

2

temperature

probe

faulty

or

disconnected

Auto

Prevents

the

regulations

depending on the same

Can be set

AL04

Zone

1

temperature

probe

faulty

or

disconnected

Auto

Prevents

the

regulations

depending on the same

Can be set

AL05

Zone 1 humidity sensor faulty or disconnected

Auto

Prevents

the

regulations

depending on the same

Can be set

AL06

Dehumidifier block alarm

A/M

Dehumidifier collector and

booster stop

Can be set

AL07

Day zone anti-freeze alarm

A/M

Pump activation *

1

Can be set

AL08

Zone 2 anti-freeze alarm

A/M

Pump activation *

1

Can be set

AL09

HP block alarm

A/M

Chiller-hp control block

Can be set

AL10

Chiller block alarm

A/M

Chiller-hp control block

Can be set

AL11

Chiller-hp operating hours alarm

Manu*

2

Display

-

AL12

Pump operating time alarm

Manu*

2

Display

-

AL13

Flow switch alarm

Auto*

3

Switch-off all devices

Can be set

AL14

Configuration alarm

Auto

Stops the unit

-

AL15

High temperature lock alarm

A/M

Lock all loads

Can be set

AL15

High temperature lock alarm

A/M

Lock all loads

Can be set

A/M: Automatic or Manual alarm (can be set from parameter)

(*

1

) If the zone collector activates in anti-freeze period

(*

2

) To rearm the alarms linked to the operating hours, just zero the device hours.

(*

3

) Manual alarm after a number of alarms in one hour (PA03)

Advertising