EVCO S.p.A.

c-pro 3

hecto MCSA | User manual ver. 2.0 | Code 144MCSAE204

page 43 of 52

Label

Parameter description

Default

Min

Max

PV12

Maximum external temperature in Summer mode for

calculation of the shifting set-point

30.0

10.0

70.0

PV13

Value of the shifting set-point relative to the minimum

external temperature in Summer mode

12.0

0.0

40.0

PV14

Value of the shifting set-point relative to the maximum

external temperature in Summer mode

7.0

0.0

40.0

PV15

Fixed value of the shifting set-point in Summer mode if the

function is disabled due to alarm

7.0

0.0

40.0

PV16

Minimum external temperature in Winter mode for calculation

of the shifting set-point

-5.0

-30.0

30.0

PV17

Maximum external temperature in Winter mode for calculation

of the shifting set-point

10.0

0.0

30.0

PV18

Value of the shifting set-point relative to the minimum

external temperature in Winter mode

35.0

0.0

90.0

PV19

Value of the shifting set-point relative to the maximum

external temperature in Winter mode

25.0

0.0

90.0

PV20

Fixed value of the shifting set-point in Winter mode if the

function is disabled due to alarm

35.0

0.0

90.0

PV21

Mixing valve operating mode (summer):

0 : Closed

1 : Modulating

2 : Open

1

0

2

PV22

Mixing valve operating mode (winter):

0 : Closed

1 : Modulating

2 : Open

1

0

2

PV23

Mixing valve fixed opening

20.0

0.0

100.0

PV24

Opening for mixing valve anti-grip

100.0

0.0

100.0

PV25

Mixing valve regulation valve

5.0

0.0

10.0

PV26

Mixing valve regulating integral time (seconds)

0

0

999

INSTALLER PARAMETERS - ALARMS

PA01

Flow switch alarm delay on start-up (seconds)

30

0

255

PA02

Flow switch alarm delay (seconds)

5

0

255

PA03

Maximum number of flow switch alarms in one hour

3

0

10

PA04

Probes alarm delay

10

0

240

PA10

Pump operating time alarm enabled

1 (Yes)

0 (No)

1 (Yes)

PA11

Enable chiller-HP operating hours alarm

1 (Yes)

0 (No)

1 (Yes)

PA20

Dehumidifier block alarm rearm type

0: Auto - Automatic

1: Manu - Manual

0 (auto)

0 (auto)

1 (manu)

PA21

Dehumidifier block alarm delay (seconds)

5

0

999

PA22

Zone 1 anti-freeze alarm rear type

0: Auto - Automatic

1: Manu - Manual

0 (auto)

0 (auto)

1 (manu)

PA23

Zone 1 anti-freeze alarm delay (seconds)

5

0

999

Advertising