5.2.6

Controlling the high and low flow temperatures

Whenever the flow water temperature exceeds the maximum temperature value or drops below the minimum

temperature value allowed for the hysteresis value of the system, then the regulator will start special management

cycles for this emergency:

High temperature protection: the mixing valve is closed immediately in order to prevent overheating in the system

controlled, until the temperature returns to the maximum values allowed for the system.

Low temperature protection: after a fixed delay of 60 seconds, the circulation pump is activated to facilitate heating

the system water. The pump will remain on until the minimum temperature conditions have been recovered.

5.2.7

Flow anti-freeze protection

During winter operating mode when the system is not running (i.e. in OFF status or with time periods enabled but on a

day when the system is off), a flow anti-freeze protection control is however active.

If the external temperature goes below the pre-defined anti-freeze threshold, the system will run with special

activation cycles of the circulation pumps, in order to prevent breakages in the system due to frozen pipes.

Eternal temperature lower than -4.0 °C: flow pump always active;

External temperature between -5.0 and 1.5 °C: flow pump active 10 minutes every 6 hours;

Eternal temperature higher than 1.5 °C: flow pump off

When the external temperature is between -4.0 and -5.0 °C flow pump behaviour depends on the previous situation.

5.3

Regulation of zone humidity

5.3.1

Regulation principle

Whenever the function is enabled, during SUMMER operating mode when the relative humidity detected by the

environment humidity transducer is over the active zone humidity set-point value, the regulator will activate the

collector/dehumidification consent.

Whenever dehumidification makes use of flow water for its action (established via the relevant parameter), the

activation of the zone collector/dehumidification valve generates the same sequence of activations/controls, triggered

with zone heating/cooling.

For its operation, consult zone temperature regulation.

5.3.2

Management of the dehumidifier

The dehumidifier control is activated when the environment relative humidity value is over the active environment

humidity set-point + hysteresis value (differential).

Depending on the value assumed by parameter PD01 (Use of flow water enabled for dehumidification), as well as the

output for dehumidifier control, the circulation pump and the mixing valve can be activated.

PD01 = 0 –

only the dehumidifier control is activated

PD01 = 1 –

the dehumidifier and the circulation pump are activated

PD01 = 2 –

the dehumidifier control, the circulation pump and the mixing valve are activated

5.3.3

Zone humidity work set-point

The zone humidity set-point is decided in manual mode via the relevant user parameters present in the regulator or in

automatic mode, set by the final user via the programmed weekly time periods.

To set the automatic humidity work set-points (Economy and Comfort set-points), consult the dedicated paragraph.