User interface, 1 display and keyboard – EVCO EPH4DXP1SA User Manual

Page 17

Advertising
background image

EVCO S.p.A.

c-pro 3

hecto MCSA | User manual ver. 2.0 | Code 144MCSAE204

page 17 of 52

PGUT=3

-

zone 1 (temperature)

-

zone 2 (temperature).

I/O

Description

Zone controller

Analogue inputs

AI 1

External Temperature (NTC)

AI 2

Supply Temperature (NTC)

AI 3

Zone 2 temperature (NTC)

AI 4

Zone 1 temperature (NTC)

Serial ports

RS 485

Modbus RTU protocol

CANbus

Not used

Digital inputs (potential-free contact ON-OFF)

DI 1

Mixing circuit flow switch

DI 2

Hot block alarm boiler

DI 3

Alarm – cooling block Chiller

DI 4

Remote summer winter

DI 5

Not used

Analogue outputs (PWM/0-10V/4-20mA)

AO 1

not available

AO 2

0-10 V flow modulating valve (or 4-20 mA to be ordered)

AO 3

ON-OFF valve (2 or 3 ways) for energy recording

Digital Outputs (Relay)

DO 1

collector_zone 1

DO 2

collector_zone 2

DO 3

Hot consent (Boiler or HP)

DO 4

Cold consent (Chiller)

DO 5

Apartment flow line circulation pump control

DO 6

Alarm

3.

USER INTERFACE

3.1

Display and keyboard

The user interface is made up from a 6-key membrane keyboard with graphical 128 x 64 pixel LCD in black and white,

which gives the instrument great capacity for information combined with user-friendliness.