4 flow work set-point, 5 dew point control, Point – EVCO EPH4DXP1SA User Manual

Page 33: Dew point control

Advertising
background image

EVCO S.p.A.

5.2.4

Flow work set-point

The regulation set-point can be fixed or linked to a linear calculation on the temperature measurement of the external

air.

If the external air temperature probe is enabled and operating, then the regulation set

a climatic curve.

If the external air temperature probe is not present or broken, then the regulation set

via a relevant maintenance level parameter.

The set-point calculation climatic curve envisions setting two

These two pairs determine a minimum and maximum value of the set

per figure.

The two climatic curves and set-points differ for Summer or Winter mode, sep

seasons.

5.2.5

Dew point control

During SUMMER operating mode, the mixing valve work set

modified for the dew point control.

The dew point is the temperature at which a mass of air must be cooled at constant pressure, until it is saturated (i.e.

when the percentage of water vapour reaches 100%) and therefore can start to condensate if it should lose further

heat.

This would lead to the formation of dew on the cooled surface, thus compromising the integrity of the controlled

environment.

The dew point is calculated on the basis of the temp

To consider the construction features of the syst

be set by parameter.

The mixing valve regulation set-point (or of the flow line) will be limited to the minimum value given by the "flow dew

point + offset" calculated, whenever necessary.

If enabled, the lock alarm parameter for high and/or low temperature, after a delay set by parameter, will be disabled

all the loads.

c-pro 3

hecto MCSA | User manual ver.

page 33 of 52

point

point can be fixed or linked to a linear calculation on the temperature measurement of the external

If the external air temperature probe is enabled and operating, then the regulation set-point is calculated acco

If the external air temperature probe is not present or broken, then the regulation set-point is fixed; it is established

via a relevant maintenance level parameter.

point calculation climatic curve envisions setting two pairs of External Temperature -

minimum and maximum value of the set-point depending on the external temperature, as

points differ for Summer or Winter mode, separating the valve operation in the two

Dew point control

During SUMMER operating mode, the mixing valve work set-point will be monitored continuously and, if necessary,

temperature at which a mass of air must be cooled at constant pressure, until it is saturated (i.e.

when the percentage of water vapour reaches 100%) and therefore can start to condensate if it should lose further

dew on the cooled surface, thus compromising the integrity of the controlled

The dew point is calculated on the basis of the temperature and humidity of the zone 1.

To consider the construction features of the system, the dew point will be calibrated by a pre

point (or of the flow line) will be limited to the minimum value given by the "flow dew

point + offset" calculated, whenever necessary.

arm parameter for high and/or low temperature, after a delay set by parameter, will be disabled

| User manual ver. 2.0 | Code 144MCSAE204

point can be fixed or linked to a linear calculation on the temperature measurement of the external

point is calculated according to

point is fixed; it is established

- Set-point values.

point depending on the external temperature, as

arating the valve operation in the two

point will be monitored continuously and, if necessary,

temperature at which a mass of air must be cooled at constant pressure, until it is saturated (i.e.

when the percentage of water vapour reaches 100%) and therefore can start to condensate if it should lose further

dew on the cooled surface, thus compromising the integrity of the controlled

by a pre-defined offset that can

point (or of the flow line) will be limited to the minimum value given by the "flow dew

arm parameter for high and/or low temperature, after a delay set by parameter, will be disabled