EVCO EPH4DXP1SA User Manual

Page 42

Advertising
background image

EVCO S.p.A.

c-pro 3

hecto MCSA | User manual ver. 2.0 | Code 144MCSAE204

page 42 of 52

Label

Parameter description

Default

Min

Max

INSTALLER PARAMETERS - LINE

PL01

System line type

0: low temperature

1: high temperature

1

0

1

PL02

Low temperature line set-point (summer)

18.0

7.0

30.0

PL03

Low temperature line set-point (winter)

30.0

20.0

90.0

PL04

High temperature line set-point (summer)

12.0

5.0

30.0

PL05

High temperature line set-point (winter)

60.0

25.0

90.0

PL06

Dew point offset

3.0

0.0

10.0

PL10

High temperature set-point

45.0

0.0

90.0

PL11

High temperature differential

5.0

0.0

10.0

PL12

Low temperature set-point

10.0

-10.0

40.0

PL13

Low temperature differential

5.0

0.0

10.0

PL14

Lock high temperature alarm delay (minutes)

2

0

30

PL15

Type of lock high temperature alarm

0 – No

1 – Automatic

2 - Manual

1

0

2

PL16

Lock low temperature alarm delay (minutes)

2

0

30

PL17

Type of lock low temperature alarm

0 – No

1 – Automatic

2 - Manual

1

0

2

PL20

Chiller-hp activation delay from system line pump O

(seconds)

60

0

255

PL21

Regulation for heating/cooling external control

0: Valve lateral band

1: Valve maximum opening

2: Valve minimum opening

2

0

2

PL22

Chiller-hp switch-off delay with active zones request

(minutes)

1

0

30

PL23

Temperature delta for pump switch-off with chiller-hp in alarm

mode

5.0

0

10.0

PL24

Chiller-hp switch-off delay without active zones request

(seconds)

10

0

255

INSTALLER PARAMETERS - PUMP

PP01

Enable pump anti-grip cycle

1 (Yes)

0 (No)

1 (Yes)

PP02

System line pump On delay (seconds)

30

0

255

PP03

System line pump Off delay (seconds)

60

0

255

INSTALLER PARAMETERS - VALVE

PV01

Enable valve anti-grip cycle

1 (Yes)

0 (No)

1 (Yes)

PV02

Valve delay from System line pump ON

30

0

255

PV05

Valve min value

0.0

0.0

100.0

PV06

Valve max value

100.0

0.0

100.0

PV11

Minimum external temperature in Summer mode for

calculation of the shifting set-point

10.0

0.0

30.0