EVCO S.p.A.

c-pro 3

hecto MCSA | User manual ver. 2.0 | Code 144MCSAE204

page 11 of 52

-

connect the termination of the CAN port (120

, 0.5 W); position micro switch 1 in the ON position in order to connect the

CAN port termination (connect the termination of the first and last network element termination).

Note: switches n° 1, 2 and 3 are not used in this application

.

CAN BUS

CAN port.

Clamp

Meaning

CAN +

+ signal

CAN -

- signal

GND

earth

The maximum number of devices that can make up the CAN network (32) depends on the bus load; the bus load

depends on the CANbus communication baud rate and the type of device in the network.

For example: a CAN network can be made up from a programmable controller, four I/O expansions and four user terminals

with 500,000 baud rate.

The maximum length of the CAN port connection cables depends on the CANbus communication baud rate, as follows:

-

1,000 m (3,280 ft) with baud rate of 20,000 baud

-

500 m (49,987.20 cm) with baud rate of 50,000 baud

-

250 m (24,993.60 cm) with baud rate of 125,000 baud

-

50 m (164 ft) with baud rate of 500,000 baud.

Connect the CAN port using a twisted pair cable.

For the settings relative to the CAN port, see chapter 6 “CONFIGURATION”.

DIGITAL OUTPUTS

Digital outputs 1, 2, 3, 4 and 5 (electro-mechanical relays).

Clamp

Meaning

CO1/2

common digital outputs 1 and 2

NO1

digital output 1 normally open contact

NO2

digital output 2 normally open contact

NO3

digital output 3 normally open contact

CO3/4/5

common digital output 3/4/5