EVCO EPH4DXP1SA User Manual

Page 41

Advertising
background image

EVCO S.p.A.

c-pro 3

hecto MCSA | User manual ver. 2.0 | Code 144MCSAE204

page 41 of 52

Label

Parameter description

Default

Min

Max

PZ22

Zone 1 climatic curve max. ext T. (summer)

35.0

0.0

70.0

PZ23

Zone 2 climatic curve min. ext T. (summer)

12.0

0.0

70.0

PZ24

Zone 2 climatic curve max. ext T. (summer)

35.0

0.0

70.0

PZ25

Zone 1 climatic curve min. ext T. (winter)

-5.0

-30.0

40.0

PZ26

Zone 1 climatic curve max. ext T. (winter)

12.0

-30.0

40.0

PZ27

Zone 2 climatic curve min. ext T. (winter)

-5.0

-30.0

40.0

PZ28

Zone 2 climatic curve max. ext T. (winter)

12.0

-30.0

40.0

PZ29

Zone 1 climatic curve set-point delta

0.0

-10.0

10.0

PZ30

Zone 2 climatic curve set-point delta

0.0

-10.0

10.0

INSTALLER PARAMETERS - COLLECTORS

PC01

Zone 1 T set differential

1.0

0.0

10.0

PC02

Zone 2 T set differential

1.0

0.0

10.0

PC03

Zone 1 H set differential

5.0

0.0

20.0

PC04

Collectors off Delay (seconds)

30

0

900

PC11

Winter automatic switch-over threshold

5.0

-30.0

40.0

PC12

Summer automatic switch-over threshold

30.0

-30.0

40.0

PC13

Summer/Winter automatic switch-over delay (minutes)

1

0

255

INSTALLER PARAMETERS - DEHUMIDIFIER

PD01

Enable use of supplywater for dehumidification:

0 = Disabled

1 = Enabling complete chain

2 = Enabling heating/cooling only

1

0

2

PD02

Booster/dehumidifier restriction

1 (Yes)

0 (No)

1 (Yes)

PD03

Booster mode

0: None

1: Cooling

2: Heating

3: Cooling/Heating

3

0

3

PD04

Heating booster assignment

0: None

1: zone 1

2: zone 2

3: zone 1/zone 2

3

0

3

PD05

Cooling booster assignment

0: None

1: zone 1

2: zone 2

3: zone 1/zone 2

3

0

3

PD10

Zone 1 integration delta (winter)

1.0

0.0

10.0

PD11

Zone 1 integration delay (winter)

5

1

255

PD12

Zone 1 integration delta (summer)

1.0

0.0

10.0

PD13

Zone 1 integration delay (summer)

5

1

255

PD14

Zone 2 integration delta (winter)

1.0

0.0

10.0

PD15

Zone 2 integration delay (winter)

5

1

255

PD16

Zone 2 integration delta (summer)

1.0

0.0

10.0

PD17

Zone 2 integration delay (summer)

5

1

255