EVCO c-pro kilo AHU User Manual

Page 18

Advertising
background image

C-PRO KILO AHU APPLICATION MANUAL

Pag. 18

Conn.

Label

Description

JA-1

AI1

Analogue input n.1 (for NTC probe)

JA-2

AI2

Analogue input n.2 (for NTC probe)

JA-3

AI3

Analogue input n.3 (for NTC probe)

JA-4

AI4

Analogue input n.4 (for NTC probe / transducers 0-20 mA /
transducers 4-20 mA); ratiometric transducers 0-5 V upon
request

JA-5

AI5

Analogue input n.5 (for NTC probe / transducers 0-20 mA /
transducers 4-20 mA); ratiometric transducers 0-5 V upon
request

JA-6

GND

Common analogue inputs

JA-7

+5V

Supplying power to ratiometric transducers

JA-8

+12V

Supplying current to transducers

JB

Connector for the digital signals

Conn.

Label

Description

JB-1

ID1

Digital input n.1

JB-2

ID2

Digital input n.2

JB-3

ID3

Digital input n.3

JB-4

ID4

Digital input n.4

JB-5

ID5

Digital input n.5

JB-6

ID6

Digital input n.6

JB-7

ID7

Digital input n.7

JB-8

GND

Common digital inputs

JD:

Connector for cut-phase output EVDFAN1 (analogue output 1)

Conn.

Label

Description

JD-1

VDC

Supplying power to cut-phase module EVDFAN1

JD-2

AO1

Cut-phase module output EVDFAN1


In order to utilize the cut-phase module EVDFAN1, it is necessary to supply the expansion
with an alternate current; the phase which supplies power to the controller must be the same
as that which is supplied to both the expansion and the module.

JE:

Connector for the analogue outputs 2 and 3 (for isolation); upon request, not available in

daytime models

Conn.

Label

Description (Version V+I)

JE-1

AO2

0-10VDC

JE-2

GND

Common analogue outputs

JE-3

AO3

4-20mA

Description (Versione I+I)

JE-1

AO2

4-20 mA

JE-2

GND

Common analogue outputs

JE-3

AO3

4-20 mA

Description (Versione V+V)

JE-1

AO2

0-10VDC

JE-2

GND

Common analogue outputs

JE-3

AO3

0-10VDC

Advertising