2 modulating regulation – EVCO c-pro kilo AHU User Manual

Page 53

Advertising
background image

C-PRO KILO AHU APPLICATION MANUAL

Pag. 53


SUMMER operating mode



WINTER operating mode



Note.
It is necessary to set the positions of the two digital outputs for the fan’s parameter
HF01(delivery) and HF02(pickup). If a parameter is equal to zero the signal from the relative
fan will not be enabled on any digital output.

6.5.2 Modulating Regulation

Generally controlled by an inverter, it carries out a refined heating control (funz. invernale)
“winter operating mode” or cooling function (funz. estivo) “summer operating mode” from
the central unit particularly focused on saving energy. The regulation and operation of the
regulation Set Point (SEtC, SEtH) is that of a differential (PF02) which is compared to the
ambient temperature reading, or on the pickup channel according to where the regulation
probe is positioned. In order to set this regulation select PF01=2.
Each mode of operation (summer/winter) has its own distinct regulation.











SEtC (SEtH): Set Point

OFF

T. Ambient

PF02: Diff.

ON

SEtH: Set Point

OFF

T. Ambient

PF02: Diff.

ON