1 alarm off status – EVCO c-pro kilo AHU User Manual
Page 41
Advertising
![background image](/manuals/675451/41/background.png)
C-PRO KILO AHU APPLICATION MANUAL
Pag. 41
6.1.1 Alarm OFF status
When the machine is turned on an additional status, OFF da alarm (Alarm Off) exists. This
shuts down the unit, all devices, and closes the external air shutters completely until the alarm
conditions are restored. The central alarm will shut down to OFF status if there is no digital /
supervisor consent or shut down is requested via the keyboard. The alarms which provoke
this status are as follows:
-
Fan thermal alarm
-
Fan inverter alarm
-
Air Flow Meter alarm
-
Fire/smoke alarm
Once alarm conditions have been restored the machine will return to normal operation.
Advertising