EVCO c-pro kilo AHU User Manual

Page 85

Advertising
background image

C-PRO KILO AHU APPLICATION MANUAL

Pag. 85

770

PackedAlarm_2

0

0

65535

Bit1=AL17,
Bit2=AL18,
Bit3=AL19,
Bit4=AL20,
Bit5=AL21,
Bit6=AL22,
Bit7=AL23,
Bit8=AL24,
Bit9=AL25,
Bit10=AL26,
Bit11=AL27,
Bit12=AL30,
Bit13=AL31

R/W

1025

Status_OnOff_bySUP

0

0

1

R/W

1026

Status_MOde_bySUP

0

0

1

R/W

1027

Status_En_OffsetSP_bySUP

0

0

1

R/W

1281

CLOCK_RTC ( Low )

0

0

214748364

7

R/W

1282

CLOCK_RTC ( High )

1283

StatusUnit

0

0

5

R/W

1284

v_MOdE

0

0

1

R/W

1285

actual_Winter_Unique_SetPoint

0.0

-15.0

158.0

Winter Set Point
or Set Point
unique(if selected
by PH27)

R/W

1286

actual_SummerSetPoint

0.0

-15.0

158.0

R/W

1287

actual_SupplySetPoint

0.0

-15.0

158.0

R/W

1288

Status_SupplyFan

0

0

6

0=Disabilitato,
1=OFF, 2=Wait
ON, 3=ON,
4=Wait OFF,
5=ALL,
6=Manual

R/W

1289

Status_ReturnFan

0

0

6

0=Disabilitato,
1=OFF, 2=Wait
ON, 3=ON,
4=Wait OFF,
5=ALL,
6=Manual

R/W

1290

Status_Humidifier

0

0

7

0=Disabilitato,
1=OFF, 2=Wait
ON, 3=ON,
4=Wait OFF,
5=ALL,
6=Manual,
7=OFFt

R/W

1291

Status_Pump

0

0

5

R/W

1292

actual_SetPoint_Shutter

0.0

-15.0

158.0

Advertising