6regulations, 1 unit status – EVCO c-pro kilo AHU User Manual

Page 40

Advertising
background image

C-PRO KILO AHU APPLICATION MANUAL

Pag. 40

6

REGULATIONS

6.1

Unit status


There are additional procedures for the start-up/shut-down of the unit:

1)

Using the On/Off key (parameter, PH05=1)

Startup: press the related key for approximately 2 seconds: if all the other enabled
conditions are present, the machine will turn “ON”.
Shutdown: press the related key for approximately 2 seconds: the machine will turn
“OFF”.

2)

Using the On/Off command from the Digital inputs (parameter, PH07=1)

Startup: close the remote On/Off contact: if all the other enabled conditions are
present, the machine will turn “ON”.
Shutdown: if the remote On/Off contact opens, the machine will turn “OFF from
Digital inputs” (as also indicated by the dictation “OFF_D”).

3)

Using the supervision protocol (parameter, PH09=1)

Startup: activate from protocol the startup status: if all the other enabled conditions
are present, the machine will turn “ON”.
Shutdown: if the startup status becomes deactivated from the protocol, the machine
will turn “OFF da protocollo di supervisione” (OFF from supervision protocol) (as
also indicated by the dictation “OFF_S”).


The status of the On/Off key has priority with respect to the other two keys. In fact, the
status of the On/Off from Digital Inputs and from supervision protocol are accessible only
when the machine’s keyboard is turned on.

A machine with its Digital inputs shut off can:

Change to OFF status by pressing the ESC key.

Change to OFF status as supervisor if you re-enter the conditions of OFF from Digital
inputs and set the status of OFF from supervisor.

Change to ON status if you re-enter the conditions of OFF from Digital inputs and do
not set the status of OFF from supervisor.


A machine with its supervision protocol shut off can:

Change to OFF status by pressing the ESC key.

Change to status OFF from Digital inputs if you re-enter the conditions of OFF from
supervisor and switch the status of OFF from Digital inputs.

Change to ON status if you re-enter the conditions of OFF from supervisor and the
conditions of OFF from Digital inputs are not present.

The machines On/Off key is the ESC key, which needs to be pressed down for approximately
2 seconds.
The remote On/Off inputs (if present) can be configured through the following parameters:

-

PH07: Enable the function

-

PH50: Set the logic NC, NO for the digital contacts

-

Hd01: Set the position for the Digital inputs

Advertising