C-PRO KILO AHU APPLICATION MANUAL
Pag. 36
modes utilizing the keyboard (ModE parameter)
PH07
Enable machine start-up/shut-down using the
Digital inputs
YES (1)
NO (0)
YES (1)
-
IS-V
PH08
Enable the change in summer/winter operating
modes utilizing the Digital inputs
NO (0)
NO (0)
YES (1)
-
IS-V
PH09
Enable machine start-up/shut-down as
supervisor
NO (0)
NO (0)
YES (1)
IS-V
PH10
Enable the change in summer/winter operating
modes as supervisor
NO (0)
NO (0)
YES (1)
IS-V
PH11
Modbus card address
1
1
247
-
IS-V
PH12
Baud Rate of comunication for the card
(0=1200, 1=2400, 2=4800, 3=9600, 4=19200)
3
0
4
-
PH13
ModBus parity (0=none, 1=Odd, 2=Even)
2
0
2
-
IS-V
PH14
Stop Bit ModBus (0=1bit, 1=2bit)
0
0
1
-
IS-V
PH18
Cancel alarm history
NO (0)
NO (0)
YES (1)
-
IS-V
Set SI (1) and
wait for value
NO (0)
PH25
Enable variation Set Point from Digital inputs
NO (0)
NO (0)
YES (1)
-
IS-V
PH26
Enable variation Set Point as Supervisor
NO (0)
NO (0)
YES (1)
-
IS-V
PH27
Enable distinct/single Set Point for
heating/cooling:
0: Set Point distinct
1: Set Point single
0
0
1
-
IS-V
If PH27=1
(single Set
Point), the
single Set
Point utilized
for the
regulation is
SEtH.
PH28
Enable nocturnal operating mode for the
modification of the Set Point regulation
NO (0)
NO (0)
YES (1)
-
IS-V
PH32
Unit of measurement of temperature:
0: °Celsius
1: °Fahrenheit
0 (°C)
0 (°C)
1 (°F)
-
IS-V
PH33
Unit of measurement of pressure:
0: Bar
1: psi
0 (Bar)
0 (Bar)
1 (psi)
-
IS-V
PH34
Value of the Atmospheric Pressure
1013
0
10000
hPa
IS-V
PH37
PPM transducer minimum value CO2/VOC
0
0
10000
ppm
IS-V
PH38
PPM transducer maximum value CO2/VOC
2000
0
10000
ppm
IS-V
PH40
Enable external temperature probe
NO (0)
NO (0)
YES (1)
-
IS-V
PH41
Enable ambient air humidity probe
0: Disabled
1: Enabled with sensor 4..20mA
2: Enabled with sensor 0..5V
1
0
2
-
IS-V
PH42
Enable air expulsion temperature probe
YES (1)
NO (0)
YES (1)
-
IS-V
PH43
Enable anti-freeze temperature probe
NO (0)
NO (0)
YES (1)
-
IS-V
PH45
Enable pre-heating air temperature probe
NO (0)
NO (0)
YES (1)
-
IS-V
PH46
Enable air quality probe (CO2/VOC)
0: Disabled
1: Enabled with sensor 4..20mA
2: Enabled with sensor 0..5V
0
0
2
-
IS-V
PH47
Enable external air humidity probe
0: Disabled
1: Enabled with sensor 4..20mA
2: Enabled with sensor 0..5V
0
0
2
-
IS-V
PH50
Logistics of Digital inputs for:
- change in summer/winter modes
- On/Off remote
- change in Set Point of regulation
NO (0)
NO (0)
NC (1)
-
IS-V
PH51
Logistics of Digital inputs used for the alarms
NO (0)
NO (0)
NC (1)
-
IS-V