C-PRO KILO AHU APPLICATION MANUAL

Pag. 36

modes utilizing the keyboard (ModE parameter)

PH07

Enable machine start-up/shut-down using the
Digital inputs

YES (1)

NO (0)

YES (1)

-

IS-V

PH08

Enable the change in summer/winter operating
modes utilizing the Digital inputs

NO (0)

NO (0)

YES (1)

-

IS-V

PH09

Enable machine start-up/shut-down as
supervisor

NO (0)

NO (0)

YES (1)

IS-V

PH10

Enable the change in summer/winter operating
modes as supervisor

NO (0)

NO (0)

YES (1)

IS-V

PH11

Modbus card address

1

1

247

-

IS-V

PH12

Baud Rate of comunication for the card
(0=1200, 1=2400, 2=4800, 3=9600, 4=19200)

3

0

4

-

PH13

ModBus parity (0=none, 1=Odd, 2=Even)

2

0

2

-

IS-V

PH14

Stop Bit ModBus (0=1bit, 1=2bit)

0

0

1

-

IS-V

PH18

Cancel alarm history

NO (0)

NO (0)

YES (1)

-

IS-V

Set SI (1) and
wait for value
NO (0)

PH25

Enable variation Set Point from Digital inputs

NO (0)

NO (0)

YES (1)

-

IS-V

PH26

Enable variation Set Point as Supervisor

NO (0)

NO (0)

YES (1)

-

IS-V

PH27

Enable distinct/single Set Point for
heating/cooling:
0: Set Point distinct
1: Set Point single

0

0

1

-

IS-V

If PH27=1
(single Set
Point), the
single Set
Point utilized
for the
regulation is
SEtH.

PH28

Enable nocturnal operating mode for the
modification of the Set Point regulation

NO (0)

NO (0)

YES (1)

-

IS-V

PH32

Unit of measurement of temperature:
0: °Celsius
1: °Fahrenheit

0 (°C)

0 (°C)

1 (°F)

-

IS-V

PH33

Unit of measurement of pressure:
0: Bar
1: psi

0 (Bar)

0 (Bar)

1 (psi)

-

IS-V

PH34

Value of the Atmospheric Pressure

1013

0

10000

hPa

IS-V

PH37

PPM transducer minimum value CO2/VOC

0

0

10000

ppm

IS-V

PH38

PPM transducer maximum value CO2/VOC

2000

0

10000

ppm

IS-V

PH40

Enable external temperature probe

NO (0)

NO (0)

YES (1)

-

IS-V

PH41

Enable ambient air humidity probe
0: Disabled
1: Enabled with sensor 4..20mA
2: Enabled with sensor 0..5V

1

0

2

-

IS-V

PH42

Enable air expulsion temperature probe

YES (1)

NO (0)

YES (1)

-

IS-V

PH43

Enable anti-freeze temperature probe

NO (0)

NO (0)

YES (1)

-

IS-V

PH45

Enable pre-heating air temperature probe

NO (0)

NO (0)

YES (1)

-

IS-V

PH46

Enable air quality probe (CO2/VOC)
0: Disabled
1: Enabled with sensor 4..20mA
2: Enabled with sensor 0..5V

0

0

2

-

IS-V

PH47

Enable external air humidity probe
0: Disabled
1: Enabled with sensor 4..20mA
2: Enabled with sensor 0..5V

0

0

2

-

IS-V

PH50

Logistics of Digital inputs for:
- change in summer/winter modes
- On/Off remote
- change in Set Point of regulation

NO (0)

NO (0)

NC (1)

-

IS-V

PH51

Logistics of Digital inputs used for the alarms

NO (0)

NO (0)

NC (1)

-

IS-V