C-PRO KILO AHU APPLICATION MANUAL

Pag. 35

PA01

Enable alarms during hours of fan operation

YES (1)

NO (0)

YES (1)

-

IS-S

PA02

Enable alarms during hours of pump operation

NO (0)

NO (0)

YES (1)

-

IS-S

PA03

Signal alarms during hours of operation on
alarm relay

YES (1)

NO (0)

YES (1)

-

IS-S

PA04

Probe alarm delay

10

0

240

Sec

IS-S

PA05

Signal alarm probe on alarm relay

YES (1)

NO (0)

YES (1)

-

IS-S

PA06

Expansion alarm delay

5

0

999

Sec

IS-S

PA08

Signal delivery fan alarm on alarm relay

YES (1)

NO (0)

YES (1)

-

IS-S

PA09

Signal pickup fan alarm on alarm relay

YES (1)

NO (0)

YES (1)

-

IS-S

PA10

Alarm delay thermal fans

2

0

999

Sec

IS-S

PA11

Alarm delay inverter fans

2

0

999

Sec

IS-S

PA15

Alarm delay thermal pumps

2

0

999

Sec

IS-S

PA16

Signal alarms thermal pumps on alarm relay

YES (1)

NO (0)

YES (1)

-

IS-S

PA20

Type of pressure switch alarm re-arm (dirty
recuperator)
0: Auto - Automatic
1: Manu - Manual

Manu (1)

Auto (0)

Manu (1)

-

IS-S

PA21

Pressure switch alarm delay (dirty recuperator)

30

0

999

Sec

IS-S

PA24

Type of alarm re-arm pressure switch air filter
0: Auto - Automatic
1: Manu - Manual

Manu (1)

Auto (0)

Manu (1)

-

IS-S

PA25

Pressure switch air filter alarm delay

30

0

999

Sec

IS-S

PA26

Signal alarms pressure switch air filter alarm
relay

YES (1)

NO (0)

YES (1)

-

IS-S

PA28

Reset airflow meter alarm delay

30

0

999

Sec

IS-S

PA29

Airflow meter alarm delay

5

0

999

Sec

IS-S

PA30

Signal alarm air flow meter on alarm relay

YES (1)

NO (0)

YES (1)

-

IS-S

PA31

Type of humidifier alarm re-arm
0: Auto - Automatic
1: Manu - Manual

Auto (0)

Auto (0)

Manu (1)

-

IS-S

PA32

Humidifier alarm delay

2

0

999

Sec

IS-S

PA33

Signal alarms humidifier on alarm relay

YES (1)

NO (0)

YES (1)

-

IS-S

PA35

Type of anti-freeze alarm management:
0: Disabled
1: From digital contact
2: From anti-freeze probe

1

0

2

-

IS-S

PA36

Alarm delay anti-freeze

5

0

999

Sec

IS-S

PA37

Signal alarm anti-freeze on alarm delay

YES (1)

NO (0)

YES (1)

-

IS-S

PA38

Activation Set Point for anti-freeze alarm from
transducer

2.0

PH03

PH04

°C

IS-S

PA39

Activation differential for anti-freeze alarm from
transducer

3.0

0.0

10.0

°C

IS-S

PA40

Enable RTC alarm

YES (1)

NO (0)

YES (1)

IS-S

PA41

Type of RTC alarm restoration
0: Auto - Automatic
1: Manu - Manual

Manu (1)

Auto (0)

Manu (1)

-

IS-S

PA42

Signal RTC alarms on alarm relay

YES (1)

NO (0)

YES (1)

-

IS-S

PA45

Signal alarms fire/smoke on alarm relay

YES (1)

NO (0)

YES (1)

-

IS-S

VARIOUS PARAMETERS

PH01

Minimum value threshold for the pressure
probe

0

-10.0

PH02

Bar

IS-V

PH02

Maximum value threshold for the pressure
probe

30.0

PH01

45.0

Bar

IS-V

PH03

Minimum temperature value for the Set Point

-5.0

-15.0

PH04

°C

IS-V

PH04

Maximum temperature value for the Set Point

40.0

PH03

70.0

°C

IS-V

PH05

Enable machine start-up/shut-down by pressing
the ESC/Stand-By key

YES (1)

NO (0)

YES (1)

-

IS-V

PH06

Enable the change in summer/winter operating

YES (1)

NO (0)

YES (1)

-

IS-V