EVCO c-pro kilo AHU User Manual

Page 37

Advertising
background image

C-PRO KILO AHU APPLICATION MANUAL

Pag. 37

PH52

Logistics of Digital inputs used for the alarm
flux status

NC (1)

NO (0)

NC (1)

-

IS-V

PH53

Logistics of Digital inputs for alarm fire-smoke

NC (1)

NO (0)

NC (1)

-

IS-V

PH60

Logistics of alarm relay

NO (0)

NO (0)

NC (1)

-

IS-V

PH15

Restoring the manufacturers’ defualt parameters

NO (0)

NO (0)

YES (1)

-

IS-D

Wait for the
value NO(0)
upon
completion of
restore

PSd3

Password Installation Operator Level (3)

0

-999

9999

-

IS

Level

4

CONSTRUCTOR MENU

CONFIGURATION PARAMETERS

Upon modification of these parameters it is

advised to remove and delete the card feed

PG00

Unit type:
1: Winter operating mode only
2: Summer operating mode only
3: Winter and summer operating mode with
humidity
4: Winter and summer operating mode with
humidity and heat recuperation
5: Two coils without dehumidification
6: Three coils with dehumidification

3

1

6

-

CO-W

PG01

Number of coils
1: Heating/Cooling (Unit with single coil)
2: Heating, Cooling
3: Heating, Cooling, Post-Heating

1

1

3

-

COW

If PG01=1 the
MOdE
parameter
decides if hot
or cold

PG02

Enable the presence of the expansion

NO (0)

NO (0)

YES (1)

-

CO-W

PG03

Enable RTC system clock

YES (1)

NO (0)

YES (1)

-

CO-W

If PG03=0,
history does
not memorize
elements and
the nocturnal
operating
mode is
disabled

PG04

Primary types of regulation:
0: On fan
1: On valves

Valv. (1)

Fan (0)

Valv. (1)

-

CO-W

PG05

Positioning probe of regulation:
0: Ambient probe
1: Probe in restart channel

Amb. (0)

Amb. (0)

Rest. (1)

-

CO-W

PG06

Enable humidifier
0: Disabled
1: Regulation ON-OFF
2: Regolation Modulating

1

0

2

-

CO-W

PG07

Enabled external air shutters
0: Disabled
1: Modulating regulation
2: Fixed opening

1

0

2

-

CO-W

PG08

Enable delivery fans

YES (1)

NO (0)

YES (1)

-

CO-W

PG09

Enable pickup fans

YES (1)

NO (0)

YES (1)

-

CO-W

PG10

Enable heating circulation pump (or single pump
for the unit at single coil)

NO (0)

NO (0)

YES (1)

-

CO-W

PG11

Enable cooling circulation pump

NO (0)

NO (0)

YES (1)

-

CO-W

PG12

Enable dehumidification

NO (0)

NO (0)

YES (1)

-

CO-W

PG13

Manage heating recuperator

0

0

4

-

CO-W

Advertising