EVCO c-pro kilo AHU User Manual

Page 87

Advertising
background image

C-PRO KILO AHU APPLICATION MANUAL

Pag. 87

1562

PM26_EnManualHumidifier

0

0

1

R/W

1563

PM27_ForceHumidifier

0

0

100

R/W

1564

PM80_Calibration_EnvironmentProbe

0.0

-9.9

50.0

R/W

1565

PM81_Calibration_AirSupplyProbe

0.0

-9.9

50.0

R/W

1566

PM82_Calibration_AirExternalProbe

0.0

-9.9

50.0

R/W

1567

PM83_Calibration_HumidityEnvironment_Probe

0

-9

9

R/W

1568

PM84_Calibration_AirSupplyPressure_Probe

0.0

-14.5

14.5

R/W

1569

PM90_LastMaintainDATE ( Low )

252460801

2524608

01

214748364

7

R/W

1570

PM90_LastMaintainDATE ( High )

1571

PC01_EnableSetPointCompensation

0

0

1

R/W

1572

PC02_MaxSetPoint_Compensation

28.0

-15.0

158.0

R/W

1573

PC03_SetPointExternal_StartCompensation

26.0

-15.0

158.0

R/W

1574

PC04_OffsetSetPointExternal_Compensation

4.0

0.0

68.0

R/W

1575

PC05_Enable_SniffingMode

0

0

1

R/W

1576

PC06_WaitTime_SniffingCycle

6

1

99

Minute

R/W

1577

PC07_ActiveTime_SniffingCycle

2

1

30

Minute

R/W

1578

PC08_EnableBothFans_onSniffing

0

0

1

R/W

1579

PF01_FanRegulationType

1

0

3

0=Continue,
1=On/Off,
2=Inverter,
3=Inverter+On/O
ff

R/W

1580

PF02_FanRegulation_Diff

5.0

0.0

86.0

R/W

1581

PF03_MinSpeedFan

0.00

0.00

100.00

R/W

1582

PF04_MaxSpeedFan

100.00

0.00

100.00

R/W

1583

PF05_Fan_TonOther

20

0

999

R/W

1584

PF08_FanRegulation_InverterOnOff_Diff

2.00

0.00

60.00

R/W

1585

PF09_FanRegulation_InverterOnOff_Time

10

0

999

R/W

1586

PF10_ForceOnErrorProbe

30.00

0.00

100.00

R/W

1587

PV01_Valve_BP

10.0

0.0

86.0

R/W

1588

PV02_Valve_Ti

0

0

999

R/W

1589

PV05_Offset_ValveSupplySetPoint

0.0

0.0

50.0

R/W

1590

PV06_Diff_ValveSupplySetPoint

5.0

0.0

68.0

R/W

1591

PV10_ForceValve_OnErrorProbe

30.00

0.00

100.00

R/W

1592

PS01_TypeRegulation_AirExternalShutter

0

0

1

0=Moduling,

R/W

Advertising