C-PRO KILO AHU APPLICATION MANUAL

Pag. 67


Note. It is necessary to enable the utilization of the external air temperature probe (PH40=1).
If the probe is in error the regulation is disabled.

6.11.3 Enable Free-Cooling and Free-Heating heat exchanger

The heat content regulation also considers the air humidity to enable the free-cooling and
free-heating processes. In order to utilize this function you must set PS01=2 and it is
necessary to enable the ambient humidity probes (PH41=1), external temperature (PH40=1)
and external air humidity (PH47=1). Additionally, it is necessary to set the value of the
atmospheric pressure in hPa (parameter PH34). The regulation provides the calculation of the
external heat content (HExt) and ambient heat content (HAmb).
The calculation of the heat content is done using the temperature value and the humidity
value utilizing the atmospheric pressure to achieve a more precise calculation. The
differential Set Point (PS16) and relative hysteresis (PS15) must be set in order to enable at
the regulation.
To enable see graphs below:


Note. If one of the probes in use are in error or if the regulation has not been configured it
will be disabled. This regulation can be used only in the presence of a external air humidity
probe which has been configured on the expansion; therefore this function can be utilized
only if the expansion is enabled (PG02=1).


PS12: Diff.

T. Ambient – T. External

T. External – T. Ambient

PS13: SetFC

PS12: Diff.

PS13: SetFH

Enable Free-Cooling in temperature

Enable Free-Heating in temperature

PS15

HAmb – HExt

HExt – HAmb

PS16: SetFCHeat
exchanger

PS15

Enable Free-Cooling heat exchanger

Enable Free-Heating heat exchanger

PS16: SetFHHeat
exchanger