EVCO c-pro kilo AHU User Manual

Page 46

Advertising
background image

C-PRO KILO AHU APPLICATION MANUAL

Pag. 46

6.2.4 Unit for operation in WINTER/SUMMER with humidity
and recuperation (PG00=4)


The MOdE parameter starts while set on default on WINTER
Unit at single coil PG01=1.
The regulation of the fans starts while set on default on inverter with On/Off (PF01=3).
The primary regulation starts while set on default on the valve (PG04=1).
The regulation of the shutter is enabled for free-cooling/free-heating (PG07=1, PS01=1).
The recuperator in use is that at cross flow PG13=1.

PIN

ANALOGUE INPUTS

AI1

Ambient air temperature probe (NTC)

AI2

Air delivery temperature probe (NTC)

AI3

External air temperature (NTC)

AI4

Ambient humidity probe (4..20 mA)

AI5

Expulsion air temperature probe (NTC)

PIN

DIGITAL INPUTS

DI1

On/Off remote

DI2

Summer/winter remote commutation

DI3

Thermal delivery fan

DI4

Pressure switch recuperator dirty

DI5

Anti-freeze thermostat

DI6

Humidifier alarm

DI7

Thermal pickup fans

PIN

ANALOGUE OUTPUTS

AO 1

Not utilized

AO 2

Valve command heating/cooling (0-10V)

AO 3

Fans inverter command (0-10V)

PIN

DIGITAL OUTPUTS

DO1

Delivery fans

DO2

Pickup fans

DO3

Shutter by-pass recuperator

DO4

Opening of external air shutter

DO5

Closing of external air shutter

DO6

Humidifier on/off

DO7

Alarm


RTC system clock present.

Advertising