C-PRO KILO AHU APPLICATION MANUAL

Pag. 47

6.2.5 Unit with 2 coils without dehumidification (PG00=5)


The MOdE parameter starts while set by default on WINTER.
This unit provides the utilization of the expansion (PG02=1).
The regulation of the fans starts while on its default setting on the inverter with On/Off
(PF01=3).
The number of coils is PG01=2; the post-heating is managed by the resistance PG14=3.
The dehumidification is disabled PG12=0.
The regulation of the shutter is enabled for free-cooling/free-heating (PG07=1, PS01=1).
The recuperator utilized is that which is at cross flow PG13=1.

PIN

ANALOGUE INPUTS

AI1

Ambient air temperature probe (NTC)

AI2

Delivery air temperature probe (NTC)

AI3

External air temperature (NTC)

AI4

Ambient humidity probe (4..20 mA)

AI5

Expulsion air temperature probe (NTC)

AI6

Anti-freeze temperature probe (NTC)

AI7

Not utilized

AI8

Preheating air temperature probe (NTC)

AI9

Air quality probe CO2/VOC (4..20 mA)

AI10

External humidity probe (4..20 mA)


PIN

DIGITIAL INPUTS

DI1

On/Off remote

DI2

Summer/winter remote commutation

DI3

Thermal delivery fans

DI4

Dirty pressure switch recuperator

DI5

Pressure switch air filter

DI6

Airflow meter

DI7

Thermal pickup fan

DI8

Humidifier alarm

DI9

Inverter delivery fan alarm

DI10

Inverter pickup fan alarm

DI11

Heating pump alarm

DI12

Cooling pump alarm

DI13

Fire/smoke alarm

DI14

Not utilized


PIN

ANALOGUE OUTPUTS

AO 1

Not utilized

AO 2

Heating valve command (0-10V)

AO 3

Cooling valve command (0-10V)

AO 4

Not utilized

AO 5

Fans inverter command (0-10V)

AO 6

Modulating humidifier command (0-10V)