EVCO c-pro kilo AHU User Manual

Page 33

Advertising
background image

C-PRO KILO AHU APPLICATION MANUAL

Pag. 33

not present

Pb03

Neutral zone for the regulation of temperature

4.0

0.0

20.0

°C

IS-B

Pb05

Maximum shifting for Set Point calculation
running of delivery

0.0

0.0

20.0

°C

IS-B

If Pb05=0
function not
enabled

Pb06

Proportional band for the Set Point calculation
running of delivery

5.0

0.0

20.0

°C

IS-B

Pb10

Opening of heating valves alarm probe delivery

30.0

0.0

100.0

%

IS-B

Pb11

Opening of cooling valves alarm probe delivery

30.0

0.0

100.0

%

IS-B

Pb20

Insertion/release time single stage of resistance
for the post-heating

60

0

999

Sec

IS-B

HUMIDITY

Menu accessible only if PG06>0 or PG12=1

PU02

Neutral zone for the regulation of humidity

6

0

100

%

IS-U

PU03

Differential for the regulation of humidity

10

0

100

%

IS-U

PU04

Integral time for the regulation of
dehumidification (with cold coil)

0

0

999

Sec

IS-U

If PU04=0
ntegral action
not present

PU05

Enable functional limit for the dehumidification

NO (0)

NO (0)

YES (1)

-

IS-U

PU10

Enable humidifier control with delivery
temperature

YES (1)

NO (0)

YES (1)

-

IS-U

PU11

Set Point on the delivery temperature to enable
the humidifier

22.0

PH03

PH04

°C

IS-U

Only if
PU10=1

PU12

Differential on the delivery temperature to
enable the humidifier

3.0

0.0

20.0

°C

IS-U

Only if
PU10=1

VALVES

PV01

Proportional band for regulation of valves
(cooling/heating)

10.0

0.0

30.0

°C

IS-Va

PV02

Integral time for regulation of valves
(cooling/heating)

0

0

999

Sec

IS-Va

If PV02=0
integral action
not present

PV05

Maximum shifting for Set Point calculation
running of delivery

0.0

0.0

10.0

°C

IS-Va

If PV05=0
function not
enabled

PV06

Proportional band for the Set Point calculation
running of delivery

5.0

0.0

20.0

°C

IS-Va

PV10

Opening cooling/heating valves alarm probe
delivery

30.0

0.0

100.0

%

IS-Va

EXTERNAL AIR SHUTTERS
Menu accessible only if PG07>0

PS01

Type of Free-Cooling / Free-Heating
0: Disabled
1: Free-Cooling / Free-Heating in temperature
2: Free-Cooling / Free-Heating heat exchanger

1

0

2

-

IS-SE

PS02

Enable air quality control

NO (0)

NO (0)

YES (1)

-

IS-SE

PS03

Shutter command type
0: Only for Free-Cooling/Free-Heating
1: Only for controlling air quality
2: Priority to the greater of the two requests
3: Average of the two requests

0

0

3

-

IS-SE

PS04

Proportional band for the modulation of the
external air shutters

8.0

0.0

30.0

°C

IS-SE

PS05

Minimum opening for the external air shutters

0.0

0.0

PS06

%

IS-SE

PS06

Maximum opening for the external air shutters

100.0

PS05

100.0

%

IS-SE

PS07

Run time for the external air shutters from 0% to
100%

120

0

3600

Sec

IS-SE

PS08

Maximum time to maintain signal until end run
time on relay for external air shutters. Signal
will shut off once maximum time is reached

5

0

600

Sec

IS-SE