C-PRO KILO AHU APPLICATION MANUAL

Pag. 31

5.1

Directory of configuration parameters


Code

Description parameter

Default

Min

Max

UM

Menu

Note

CLOCK MENU

This menu is accessible only if PG03=1

PT01

Begin nocturnal operating mode

00:00:00

00:00:00

23:59:59

-

OR

PT02

End nocturnal operating mode

00:00:00

00:00:00

23:59:59

-

OR

PT03

Offset of Set Point nocturnal operating mode

0.0

-20.0

20.0

°C

OR

Level

1

USER MENU

MOd
E

Operating mode
0: Summer (Cooling)
1: Winter (Heating)

1

0

1

-

UT

SEtC

Set Point summer

24.0

PH03

PH04

°C

SEtH

Set Point winter/single

20.0

PH03

PH04

°C

UT

If PH27=1
(single Set
Point), the
single Set
Point utilized
for regulation
and SEtH.

PU01

Set Point for humidity management

55

0

100

%

UT

OS01

Offset at regulation Set Point from digital input

0.0

-20.0

20.0

°C

UT

If PH25=1

OS02

Offset at regulation Set Point from Supervisor

0.0

-20.0

20.0

°C

UT

If PH26=1

PSd1

Password for User Level (1)

0

-999

9999

-

UT

Level

2

MAINTENANCE OPERATOR MENU

PM00

Limit the maximum hours of fan operation.
Related alarms will sound if maximum hours are
exceeded.

20000

0

100000

Hrs.

MA-F

PM01

Hours of fan operation - delivery

0

0

100000

Hrs.

MA-F

PM02

Hours of fan operation - pickup

0

0

100000

Hrs.

MA-F

PM10

Limit the maximum hours of pump operation.
Related alarms will sound if maximum hours are
exceeded.

20000

0

100000

Hrs.

MA-F

PM11

Hours of cooling pump operation

0

0

100000

Hrs.

MA-F

PM12

Hours of heating pump operation

0

0

100000

Hrs.

MA-F

PM90

Last date of machine maintenance

-

MA-F

PM20

Manual/automatic fan operation - delivery
0: Auto – automatic operation
1: Manu – manual operation

0 (Auto)

0 (Auto)

1 (Manu)

-

MA-M

PM21

Force the value of the fan in manual operation

0.0

0

100.0

%

MA-M

If fan On/Off
set PM21>0 to
activate

PM23

Manual/automatic fan operation - pickup
0: Auto –automatic operation
1: Manu –manual operation

0 (Auto)

0 (Auto)

1 (Manu)

-

MA-M

PM24

Force the value of the fan pickup module in
manual operation

0.0

0

100.0

%

MA-M

If fan On/Off
set PM24>0 to
activate

PM26

Manual/automatic humidifier operation
0: Auto –automatic operation
1: Manu –manual operation

0 (Auto)

0 (Auto)

1 (Manu)

-

MA-M

PM27

Force the value of the humidifier in manual
operation

0

0

100

%

MA-M

If humidifier
On/Off set
PM27>0 to