C-PRO KILO AHU APPLICATION MANUAL

Pag. 34

PS09

Minimum variation regulation for operating the
external air shutters

0.0

0.0

90.0

%

IS-SE

Enabled if
PS09>0

PS10

Fixed value for opening external air shutters

50.0

0.0

100.0

%

IS-SE

Only with
fixed
regulation
(PG07=2)

PS11

Offset at Set Point during winter (at ambient
temp.) until the external air shutters remain
closed during winter operating mode

2.0

0.0

30.0

°C

IS-SE

Only with
regulation
module
(PS01=1)

PS12

Differential enabling free-cooling and free-
heating in temperature

2.0

0.0

20.0

°C

IS-SE

PS13

Differential Set Point enabling free-cooling and
free-heating in temperature

4.0

0.0

20.0

°C

IS-SE

PS15

Differential enabling free-cooling and free-
heating heat exchanger

8.0

1.0

100.0

KJ/

Kg

IS-SE

PS16

Differential Set Point enabling free-cooling and
free-heating heat exchanger

10.0

1.0

200.0

KJ/

Kg

IS-SE

PS20

Set Point – Air Quality Control

600

0

10000

ppm

IS-SE

PS21

Differential – Air Quality Control

100

0

2000

ppm

IS-SE

RECUPERATORS

Menu accessible only if PG13>0

Pr01

Differential Set Point for regulation of
recuperator

5.0

0.0

20.0

°C

IS-RH

Pr02

Differential of regulation of recuperator

3.0

0.0

20.0

°C

IS-RH

Pr03

Minimum Set Point expulsion temperature

1.0

PH03

PH04

°C

IS-RH

Pr04

Differential minimum expulsion temperature

4.0

0.0

20.0

°C

IS-RH

Pr05

By pass cycle time of recuperators at cross flow
for melting

5

1

99

Min

IS-RH

Pr07

Minimum velocity of rotating heat recuperator
velocity

0.0

0.0

Pr08

%

IS-RH

Pr08

Maximum velocity of rotating heat recuperator
velocity

100.0

Pr07

100.0

%

IS-RH

Only if
PG13=4

PUMPS

Menu accessibile only if PG10=1 or PG11=1

PP01

Types of pump regulation
0: Continuous regulation
1: Regulation On/Off

0

0

1

-

IS-P

PP02

Set Point on the regulation ramp for pump
startup

5.0

PP03

90.0

%

IS-P

PP03

Set Point on the regulation ramp for pump
shutdown

2.0

1.0

PP02

%

IS-P

Only if
PP01=1

PP04

Wait time for pump shutdown (only with
PP01=1)

10

1

99

Min

IS-P

OFF – Unit
immediately
shuts down
pump

HUMIDIFIER

This menu is accessible only if PG06=1

PU02

Type of regulation for humidifier
0: ON/OFF Regulation
1: Module Regulation

0

0

1

-

IS-U

PU03

Differential for the regulation of the humidifier

10

0

100

%

IS-U

PU10

Enable humidifier control with temperature of
delivery

YES (1)

NO (0)

YES (1)

-

IS-U

PU11

Set Point at temperature of delivery enabling
humidifier

22.0

PH03

PH04

°C

IS-U

Only if
PU10=1

PU12

Differential on the temperature of delivery to
enable humidifier

3.0

0.0

20.0

°C

IS-U

Only if
PU10=1

ALARM PARAMETERS