YSI 6200 User Manual

Page 104

Advertising
background image

YSI 6200 DAS

USER Manual

YSI/Massachusetts 508.748.0366, Fax 508.748.2543

Page 9-12

Sondes

The YSI sondes are detected in a different manner from the other sensors. EcoWatch instructs
the 6200 DCP to scan and identify any SDI-12 device connected to the SDI-12 bus/port. As each
device is found the 6200 records the sondes’ setup information. This information is then used by
the 6200 DCP to create a configuration file. This file is then used to program the 6200 DCP
sensor, process and output settings automatically.

SYMPTOMS

POSSIBLE CAUSE

ACTION

REF

The sonde SDI12 address is
not 0-9 or A-F

Connect the sonde to a terminal
emulator and verify the SDI-12
address. See sonde manual for
instructions on how to set the
SDI-12 address.

3.4

EcoWatch Config
wizard unable to
detect sondes
attached to the
6200 DCP

The configuration in the 6200
DCP and EcoWatch has
changed

AutoConfig the 6200 DCP to
establish a new valid
configuration.

6.6

No 12VDC present to power
sonde

Disconnect the sonde from the
6200, use a multimeter or DVM
to check Sonde Connector pins
B to A for 12VDC.

4

Sonde field cable is damaged

Perform continuity test on field
cable, Check sonde manual for
cable diagram.

3

EcoWatch DCP
detected the
sondes but no data
is posted

Extremely long sampling
period entered in the 6200
system setup

Change sample rate to a shorter
period.

6.6

EcoWatch DCP
reports -1,000,000
as data.

Sonde is disconnected or not
giving data

Check the sonde connection,
SDI-12 address and
communication configuration.

3.4

For further sonde diagnostic testing, connect a terminal emulator directly to the 6200DCP,
access the USER menu, select the Test menu and then use the SDI-12 passthrough test
commands.
CAUTION: Once done, don’t forget to enter CONTROL Z to escape.

Power

The 6200 DCP will shut off at a voltage of 10.6VDC. It will then need at least 11.7 VDC to start
up again. This is done to protect the battery from a full discharge. Under normal conditions the
battery should remain fully charged.

SYMPTOMS

POSSIBLE CAUSE

ACTION

REF

Fuse blown

Replace fuse

4

Depleted battery

Determine what caused the
battery depletion.

4.3

No DC Voltage

Defective Battery

Check for 12.5 VDC. Replace
battery if necessary.

4.3

Advertising