Table 10: Configuration parameters for the grid injection protection relay.

Configuration parameters for the grid injection protection relay

Name

Description

Units

Enable inverse
current relay

Activation of the inverse current
protection

-

Stop time

Grid injection validation time

Seconds

Reconnection time

Reclosing time

Seconds

Max. Disconnections Maximum number of reconnections

-

Disconnect. Timeout

Maximum reconnection time

Seconds

If power is injected into the grid during the period defined by the Stop time
parameter, relay number 4 (NO (terminals 9- 10)) is desactivated (If Stop time is
programmed with the value 0 this function remains deactivated). In addition, an
orange alarm icon appears on the web site, as shown in

Figure 7

:

Figure 7:

Hardware control alarm activated.


When the current injected into the grid disappears, after the Reconnection
time,

the alarm status is deactivated.

Figure 8: Inverse current relay reconnection time.