CIRCUTOR CDP-0 User Manual

Page 31

Advertising
background image

CDP

Instruction Manual

31

Condition 2:

-If Injection Margin = 0%

 It checks whether:

Pgrid < 2 x (0.03) x Pconsumed

-If Injection Margin

≠ 0%  It checks whether:

Pgrid < 2 x Injection Margin x Pconsumed

0 < 2 x 0.03 x 6000

 this condition is met

If the 2 conditions are met, the relay closes and connects the load.


So, the CDP-G will connect the second load, as shown in

Figure 28

:

Figure 28: Single-phase installation with 3 loads to connect (Load 1 and 2 Connected).


In this situation the CDP-G maintains the system without adding or removing any
loads for the amount of time configured in the “Reconnection time” variable, in
order to achieve system stability (in this case 5 minutes).

To check if this load must be disconnected, the CDP-G waits for the amount of
time programmed in the “Min. connection time” variable and then checks if the
following condition is met:

Loads