4.3.- OPERATING EXAMPLES FOR THE CDP-G MODEL

4.3.1. SINGLE-PHASE INSTALLATION WITH 1 LOAD TO BE CONNECTED

We start with a single-phase installation in which we want to use the excess
photovoltaic production to supply 1 non-critical load, such as a heat pump.

• Load 1: 5000 W heat pump


The goal is to activate these loads during times in which there is a production
excess, thus reducing energy costs.

This is the baseline data:

Phase P. Inverter Consumption Setpoint

Current production

L1

10000 W

4000 W 40% 4000 W (40% of the nominal)



Figure 24: Single-phase installation with 1 load to connect.



The CDP-G programming is shown in

Table 11

: